Fuses - ABB LME620AI Service Instruction

Electrical linear actuators for continuous modulating control
Hide thumbs Also See for LME620AI:
Table of Contents

Advertisement

6.5

Fuses

Electronic
Unit
integr.
EAN 823
EAS822
Table 2:
6.5.1
Fuse location
6.5.1.1
Integrated electronic unit
main pcb
fuse for analog setpoint input
Fig. 20:
16
Electrical Linear Actuators for Continuous Modulating Control LME620AI / LME620AN (Contrac)
Fuse type
External fuse
Mains fuse
Analog setpoint input
heater (only f. actuators f. -
25°C ambient temperature)
External fuse
Mains fuse
Analog setpoint input
Anti condensation heater +
heater (only f. actuators f. -
25°C ambient temperature)
external fuse
mains fuse
fuse for digital output DO1,
DO2, DO3
mains fuse
Fuse
Location
dimens.
--
external
5 x 20 mm main pcb
5 x 20 mm main pcb
main pcb
5 x 20 mm
--
external
in connection
5 x 20 mm
chamber
in connection
5 x 20 mm
chamber
in connection
5 x 20 mm
chamber
--
external
in connection
5 x 20 mm
chamber
in connection
5 x 20 mm
chamber
spare fuse for mains supply
heater fuse (only for -25°C version)
Electrical Connection
U = 115 V
U = 230 V
16 A, slow
6.7 A, slow
3.15 A, slow
40 mA; fast
2 A; slow
16 A, slow
6.7 A, slow
3.15 A, slow
40 mA; fast
2 A; slow
16 A; slow
6.7 A, slow
3.15 A, slow
3 x 0.2 A; medium time lag
(68de0016)
43/68-13 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lme620an

Table of Contents