3

Configuration Parameters

PSM001 Settings Parameters

3-2
To configure the PSM module in Proficy Machine Edition under Hardware Configuration,
right click and select Add a Module, then select IC694PSM001 from the Specialty
Modules tab.
Parameter
Status Input Address
Status Input Length
Signal Input Address
Signal Input Length
Mode Control Address
Mode Control Length
Parameter Write Address
Parameter Write Length
Inputs Default
I/O Scan Set
PACSystems* RX3i Power Sync and Measurement System – February 2013
Function
Starting address in %I memory for the array of status
flags sent from the PSM module to the RX3i CPU. For
details, see page 3-10.
(Read-only.) The number of %I reference addresses
used by the PSM module. 80 bits
Starting address in %AI memory for the data reported
from the PSM module to the RX3i CPU. For details, see
page 3-14.
(Read-only.) The number of %AI reference addresses
used by the PSM module. 64 words
Starting address in %Q memory for the configuration
data that is sent every scan from the RX3i CPU to the
PSM module. For details, see page3-19.
(Read-only.) The number of %Q reference addresses
used by the PSM module. 32 bits
Starting address in %AQ memory for the location of a
single parameter and its value, which can be changed in
run mode. For details, see page 3-22.
(Read-only.) The number of %AQ reference addresses
used by the PSM module. 2 words
The state of the channel value reference addresses
when the module providing those inputs is not available
or the module collecting those inputs is not available.
Choices:
Force Off: The affected channel values are set to
zero, and all alarm flags are cleared.
Hold Last State: The affected channel values retain
the state they were in before the module became
unavailable.
The scan set, as defined in the CPU's Scan Sets tab, to
be assigned to this module. The scan set determines
how often the CPU polls the data.