Appendix On-site adjustment sheet for BAC-HD150 (proposal)
Check these items to use the system.
Control item
Object
On Off Setup
BO_xxxx01
On Off State
BI_xxxx02
Alarm Signal
BI_xxxx03
Error Code
MI_xxxx04
Operational Mode
MO_xxxx05
Setup
Operational Mode
MI_xxxx06
State
Fan Speed Setup
MO_xxxx07
Fan Speed State
MI_xxxx08
Room temp
AI_xxxx09
[Water Temp] (*6)
Set Temp
[Set Water Temp]
AV_xxxx10
(*6)
Filter Sign
[Circulating Water
BI_xxxx11
Exchange Sign] (*6)
Status
• Turn ON/OFF the specific group from BMS(*1).
INACTIVE: Stop
After doing so, check that the operation status of the group
ACTIVE: Run
renews the condition using system controller or remote
controller.
• Turn ON/OFF the specific group using system controller
INACTIVE: Stop
ACTIVE: Run
After doing so, check that the operation status of the group
renews the condition on BMS .
• Make an error on an air conditioning units of the specific
After doing so, check that the warning signal of the group
INACTIVE: Normal
turns to (ACTIVE) on BMS. (*2)
ACTIVE: Error
• Recover the error of the air conditioning units of the
After doing so, check that the warning signal of the group
turns to (INACTIVE) on BMS.
01 : Normal
• Disconnect M-NET transmission line that is connected to
02 : Other errors
03 : Refrigeration fault
After doing so, check that the error code of all groups turns
04 : Water error
to Communication error (08) on BMS. (*3)
05 : Air error
• Connect M-NET transmission line to BAC-HD150.
06 : Electronic error
After doing so, check that the error code of all groups turns
07 : Sensor fault
to Normal (01) on BMS.
08 : Communication error
(Do not perform this check when other errors occur.)
09 : System error
01 : Cooling
02 : Heating
• Change operation mode of the specific group from BMS.
03 : Fan
After doing so, check that the operation mode of the group
04 : Auto
renews the mode using system controller or remote
05 : Dry (*4)
controller.
06 : Setback
01 : Cooling
02 : Heating
• Change operation mode of the specific group using
03 : Fan
04 : Auto
After doing so, check that the operation mode of the group
05 : Dry (*4)
renews the mode on BMS.
06 : Setback
01 : Low
• Change fan speed of the specific group from BMS.
02 : High
After doing so, check that the fun speed of the group
03 : Mid 2 (*5)
renews the speed using system controller or remote
05 : Mid 1 (*5)
controller.
01 : Low
• Change fun speed of the specific group using system
02 : High
03 : Mid 2 (*5)
After doing so, check that the fun speed of the group
04 : Mid 1 (*5)
renews the speed on BMS.
• Change intake air temperature and check if the display of
°F/°C
• Make a setting of set room temperature of the specific
After doing so, check that the set room temperature of the
group renews the temperature using system controller or
°F/°C
remote controller.
• Change the set room temperature of the specific group
After doing so, check that the set room temperature of the
group renews the temperature on BMS.
• Perform something to turn on the filter sign. (*2)
INACTIVE : OFF
After doing so, check that the filter sign of the group turns to
ACTIVE : ON
ON(ACTIVE) on BMS.
- 41 -
Steps
or remote controller.
group.
specific group.
BAC-HD150.
system controller or remote controller.
controller or remote controller.
BMS and system controller/remote controller are the
same.
group from BMS.
using system controller or remote controller.
Group No. [
]
Result