I/O Area; Number Of Error Addresses; Value Of Error Addresses - Mitsubishi Electric MELSEC-Q Series User Manual

Anywire db a20 master module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

4.2.1

I/O area

The slave module requires "Address setting" which specifies the start number assigned in the transmission frame.
The settings are configured in 2-point unit. The addresses of both an input slave module (e.g. input remote I/O module)
and an output slave module (e.g. output remote I/O module) start from "0", and the area later than that number is
occupied corresponding to the number of module points.
Ex.
Assignment of two 8-point input remote I/O modules
Buffer memory address
100
(input)
H
4.2.2

Number of error addresses

The number of error IDs (addresses) is entered in 2000
Any value from 0 to 128 is entered.
4.2.3

Value of error addresses

If a disconnection or a slave module error is occurred, the error address is written to 2001
the lowest address up to 128 addresses.
This value is maintained until the disconnection error is reset or until the power is turned off.
Buffer memory address
The detected error address is classified and displayed in the memory and on the monitor according to the table below.
Hexadecimal display address
000
200
The lower 2 digits indicate the address set for the slave module.
The uppermost digit indicates the type of the slave module.
44
Bit No.
15
14
13
15
14
13
AnyWire address: 15
Occupied area by the
address 8 on the 8-point input
remote I/O module
2001
H
2002
H
2003
H
207F
H
2080
H
to 1FF
H
H
to 3FF
H
H
12
11
10
9
8
12
11
10
9
8
. ( Page 48, CHAPTER 5)
H
Description
Error address 1
Error address 2
Error address 3
Error address 127
Error address 128
Description
Address of the output slave module
Address of the input slave module or I/O combined slave module
7
6
5
4
3
7
6
5
4
3
AnyWire address: 0
Occupied area by the
address 0 on the 8-point input
remote I/O module
to 2080
in the order from
H
H
2
1
0
2
1
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-l seriesMelsec-qj51aw12d2Melsec-lj51aw12d2

Table of Contents