Specifications; Table 1.3 Power Specifications; Table 1.4.1 Ups Module Cabinet Information (Battery Built-In Cabinet Model) - Mitsubishi Electric 1100A Series Owner Technical Manual

Uninterruptible power supply system
Table of Contents

Advertisement

1.5 SPECIFICATIONS

The UPS name plate displays the rated kVA as well as nominal voltages and currents.
The nameplate is located on the top of the UPS cabinet.

Table 1.3 Power Specifications

Rated output
Power
10kVA / 9kW
20kVA / 18kW
30kVA / 27kW
40kVA / 36kW
50kVA / 45kW

Table 1.4.1 UPS Module Cabinet Information (Battery Built-in Cabinet model)

UPS
CABLE
(kVA)
ENTRY
10
BOTTOM
20
BOTTOM
* : Including Batteries
Table 1.4.2 UPS Module Cabinet Information (Standard Cabinet model)
UPS
CABLE
(kVA)
ENTRY
10
BOTTOM
20
BOTTOM
30
BOTTOM
40
BOTTOM
50
BOTTOM
1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
Input voltage
3 ph / 4 wire
120V / 208V
WIDTH
DEPTH
(in/mm)
(in/mm)
19.7 / 500
27.0 / 685
19.7 / 500
27.0 / 685
WIDTH
DEPTH
(in/mm)
(in/mm)
19.7 / 500
27.0 / 685
19.7 / 500
27.0 / 685
19.7 / 500
27.0 / 685
19.7 / 500
27.0 / 685
19.7 / 500
27.0 / 685
MITSUBISHI ELECTRIC 1100 SERIES UPS
Output voltage
3 ph / 4 wire
120V / 208V
HEIGHT
WEIGHT
(in/mm)
(lb./kg)
55.1 / 1400
683* / 310*
55.1 / 1400
728* / 330*
HEIGHT
WEIGHT
(in/mm)
(lb./kg)
55.1 / 1400
287 / 130
55.1 / 1400
331 / 150
55.1 / 1400
375 / 170
55.1 / 1400
419 / 190
55.1 / 1400
463 / 210
Page Number:
1-17
HEAT LOSS
(kBTU/h)
2.3
4.6
HEAT LOSS
(kBTU/h)
2.3
4.6
6.9
9.2
11.6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents