This UPS does not include an AC input circuit breaker (MCCB) to protect the
bypass and main input circuit. The AC input circuit breaker (MCCB) is to
be field supplied and installed. Recommended circuit breaker (MCCB)'s
specifications are as follows:
Table 1.2
Rating of AC input circuit breaker
Capacity (kVA)
10
20
30
40
50
AC input and AC output over current protection and disconnect devices shall be field
supplied and installed. DC output over current protection and disconnect device shall be
field supplied and installed.
1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 4
Input Voltage
Maximum AC Input
(VAC)
208
208
208
208
208
MITSUBISHI ELECTRIC 1100 SERIES UPS
Recommended
Rating (AAC)
Breaker (A)
30
60
90
120
150
Page Number:
1-7
40
80
110
150
200