3.4 INSTALLATION PROCEDURE
A) Note the load tolerance of the floor
Refer to Table 3.3.1 and 3.3.2 for list of UPS weights:
Table 3.3.1 List of UPS weights (Battery Built-in Cabinet model)
!
UPS Capacity (kVA)
Weight (lb.)
* : Include Batteries
NOTE
Table 3.3.2 List of UPS weights (Standard Cabinet model)
UPS Capacity (kVA)
Weight (lb.)
B) Minimum clearance required for ventilation
Right side
Left side
Back side
Top side
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
Sides
Rear
Top side
Figure 3.3 Clearance for ventilation and maintenance
31.5" (800mm)
For Maintenance
1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
10
683 *
10
313
1.0" (25 mm) (not required when sidecars are used)
1.0" (25 mm) (not required when sidecars are used)
8.0" (203 mm) (refer to Figure 3.4 for Battery Built-in Cabinet Model)
16.0" (406 mm)
31.5" (800 mm)
1.0" (25 mm)
8.0" (203 mm)
16.0" (406 mm)
16" (406mm)
For Air exhaust
and Maintenance
Side View
MITSUBISHI ELECTRIC 1100 SERIES UPS
20
728 *
20
30
357
375
8" (203mm)
For Air exhaust
Page Number:
3-4
40
50
419
463