Specifications; Table 3 Power Specifications; Table 4 Ups Module Cabinet Information - Mitsubishi Electric 1100B Series Owner Technical Manual

Table of Contents

Advertisement

1.5 SPECIFICATIONS

The UPS name plate displays the rated kVA as well as nominal voltages and currents.
The nameplate is located on the top of the UPS cabinet.

Table 3 Power Specifications

Rated output
Power
10kVA / 9kW
20kVA / 18kW
30kVA / 27kW
40kVA / 36kW
50kVA / 45kW
60kVA / 54kW
70kVA / 63kW
80kVA / 72kW

Table 4 UPS Module Cabinet Information

UPS
CABLE
(kVA)
ENTRY
TOP or
10
BOTTOM
TOP or
20
BOTTOM
TOP or
30
BOTTOM
TOP or
40
BOTTOM
TOP or
50
BOTTOM
TOP or
60
BOTTOM
TOP or
70
BOTTOM
TOP or
80
BOTTOM
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Input voltage
3 ph / 4 wire
120V / 208V
WIDTH
DEPTH
(in/mm)
(in/mm)
31.5 / 800
27.0 / 685
31.5 / 800
27.0 / 685
31.5 / 800
27.0 / 685
31.5 / 800
27.0 / 685
31.5 / 800
27.0 / 685
31.5 / 800
27.0 / 685
31.5 / 800
27.0 / 685
31.5 / 800
27.0 / 685
MITSUBISHI ELECTRIC 1100B SERIES UPS
Output voltage
3 ph / 4 wire
120V / 208V
HEIGHT
WEIGHT
(in/mm)
(lb./kg)
67.3 / 1710
499 / 226
67.3 / 1710
543 / 246
67.3 / 1710
587 / 266
67.3 / 1710
631 / 286
67.3 / 1710
675 / 306
67.3 / 1710
719 / 326
67.3 / 1710
763 / 346
67.3 / 1710
807 / 366
Page Number:
1-17
HEAT
REJECTION
(kBTU/h)
2.3
4.6
6.9
9.2
13.0
15.6
18.2
20.8

Advertisement

Table of Contents
loading

Table of Contents