Huawei NetCol8000-C070 Quick Manual page 16

Chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

6.2
(Optional) Teamwork Settings
All teamwork control parameters can be set on the master smart cooling product. Only
Teamwork group No., Air conditioner address, Enable teamwork CAN resistor, Teamwork
function and Networking mode can be set on slave smart cooling products. Other parameters
of the slave units will be modified by the master unit synchronously.
The table uses 8 smart cooling products in CAN teamwork as an example.
No.
Teamwork
Teamwork
group no.
unit address
1
1
1
2
...
...
1
8
1. Teamwork group no.: A maximum of 32 smart cooling products can be connected in a
teamwork group and a maximum of four teamwork control groups can be connected in an
RS485 network. To increase the network management system (NMS) response speed, it is
recommended that one monitoring system should connect to one teamwork control group.
2. Teamwork unit address: In a teamwork control group, each smart cooling product address
must be unique, and the address of one smart cooling product must be 1 (master smart
cooling product).
3. Teamwork CAN resistor enable: After connecting smart cooling products 1 to 32 (determined
by cable routing sequence) in series, set the parameter to Yes for the first and last smart
cooling products in the teamwork control group, and retain default values (No) for other
smart cooling products.
4. Teamwork function: Indicates whether to disable or enable the teamwork function. If disabled,
a unit operates independently. If enabled, a unit operates in team with other units.
5. Network: The networking mode set on the screen must be consistent with the actual
networking mode. Otherwise, the teamwork control function will be unavailable.
6. Total number of units: Indicates the number of precision smart cooling products in a group.
The value is an integer ranging from 1 to 32.
7. Number of running units: Specifies the number of running NetCol8000-Cs in a group. The
value ranges from 1 to the number of NetCol8000-Cs in the group.
8. Rotation function: Enable the active and standby smart cooling products to work alternately.
This function is recommended when the heat load is even. When Rotation is Enable, the
parameters for rotation period and rotation time and forced rotation can be set based on the
customer's requirements.
9. When Requirement control is set to Enable, the master smart cooling product synchronizes
operating data (parameters such as the T/H control type, temp set point, humid set point for
the master smart cooling product) to the slave smart cooling product, and all the precision
smart cooling products in the group refer to the mode delivered by the master smart cooling
product. When Requirement control is set to Disable, the master smart cooling product does
not synchronize operating data to the slave smart cooling product, and all the smart cooling
products operate based on their own requirements, not referring to the mode delivered by
the master smart cooling product.
Teamwork
CAN
Teamwork
resistor
function
enable
1
Yes
2
No
...
...
8
Yes
Item
Total
Network
number
of units
CAN
Enable
network
CAN
Enable
network
CAN
...
network
CAN
Enable
network
15
Number
Rotation
of running
function
units
6 (2
8
Enable Enable
standby)
/
/
/
...
...
...
/
/
/
Require
ment
control
/
...
/