Refer to Figure 30 for a typical wiring configuration. Although this figure applies to the
remote start/stop terminals, the same wiring arrangement is used for emergency stop,
power demand and battery temperature high.

Figure 30 Remote "Start" Contact Connections

UPS Cabinet
Relay Coil current: 10mA
Details of input contacts for remote access: IOAU-12
Terminals 3 to 4 "Remote EPO" contact input
Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped.
!
NOTE: The UPS is equipped with a selectable input contact item.
The above items are the default settings. Contact MITSUBISHI
ELECTRIC POWER PRODUCTS, INC for setup information at
NOTE
1-800-887-7830.
CAUTION: In all cases, a switch having a protective cover is recommended in
CAUTION
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Relay
Coil
24 VDC
order to reduce the possibility of accidental operation.
MITSUBISHI ELECTRIC 1100B SERIES UPS
External to
UPS Cabinet
Start
Common
Use Momentary
Switches Only
User supplied
Page Number:
2-11
Start
Switch
0.5S - 4S
ON
OFF