WARNING
The UPS must be installed and operated in a controlled environment.
An improper storage and installation environment will deteriorate insulation,
shorten component life, cause corrosion and equipment malfunctions, and can
void your warranty. The standard installation and operational environment is
as follows:

Table 1 UPS Installation and Operational Environment

Category
Acceptance Criteria
Installation
Indoors, completely weather-protected location
Location
0 – 2255 m (1524 – 2255 m requires derating, contact MEPPI)
Altitude
Ambient
32°F (0°C) to 104°F (40°C)
Temperature
Ideal operating temperature for batteries: 68°F (20°C) to 77°F (25°C)
Relative Humidity
5% to 95% with no condensation
Solid
Parameter
Contaminants
Sand
(See Note 1)
Dust/ Particulate matter
(suspension)
Dust/ Particulate matter
(sedimentation)
Parameter
Chemical
Contaminants
(Gases and
Sea salts
Vapors)
Sulfur dioxide (SO
Hydrogen sulfide (H
Wet Chlorine (Cl
relative humidity >50%
Dry Chlorine (Cl
relative humidity <50%
Hydrogen chloride (HCl)
Hydrogen fluoride (HF)
Ammonia (NH
Ozone (O
oxidants
Nitrogen oxides (NO
Aerosols
Oils
Flora and Fauna
None (no presence or risk of growing mold or fungus; negligible risk of damage
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 3
4
Mean value (See Note
2)
0
)
<0.01 PPM
2
S)
<0.003 PPM
2
)
<0.0005 PPM
2
)
<0.002 PPM
2
<0.0066 PPM
<0.001 PPM
)
<1 PPM
3
) or other
<0.002 PPM
3
)
<0.05 PPM
x
<5 PPB dry air
MITSUBISHI ELECTRIC 1100B SERIES UPS
Page Number:
Maximum value
0
3
<0.01 mg/m
2
<0.4 mg/(m
·h)
Maximum Value (See
Note 3)
0
<0.03 PPM
<0.01 PPM
<0.001 PPM
<0.01 PPM
<0.0066 PPM
<0.005 PPM
<5 PPM
<0.005 PPM
<0.1 PPM
1-6