ABB HD5-S Original Instructions Manual page 23

Three-position device
Table of Contents

Advertisement

Information for use in USA/Canada (UL)
Ambient temperature for operation
Enclosure
Electrical supply
Supply Voltage HD5-S-xxx
Overall Current consumption
For devices with field wiring leads smaller
than AWG 26 following statement shall be
provided on a separate sheet or on the
device packaging:
Information for use in UK
Importer address
Safety / Harmonized Standards
2006/42/EC – Machines, 2014/30/EU – EMC, 2011/65/EU – RoHS2, 2015/863-RoHS3
EN ISO 12100-1:2010, EN ISO 13849-1:2015, IEC 62061:2005+A1:2012+A2:2015, EN 60204-1:2018
Up to SILCL 3
UL/CSA 60947-5-1
UL/CSA 60947-5-5
Certificates
TÜV Süd
2TLC010052M0201_A
-10°C
up to +50°
(no buildup of ice)
Type 1
The device shall be supplied from an isolating transformer
having a secondary overcurrent protective device that complies
with UL 248 to be installed in the field rated max 4 Ampere.
a) Max. 5 A for voltages 0-20 V (0-28.3 V peak), or
b) 100/Vp for voltages of 20-30 V (28.3-42.4 V peak).
20.4 to 27.6 VDC, supplied from Class 2 or LVLC
< 150mA
Field wiring leads smaller than AWG 26 need to be terminated in
a terminal block or similar connection device or shall be
prepared by a wire termination.
ABB Ltd
Tower Court,
Coutaulds Way
Foleshill Enterprise Park,
Coventry
CV6 5NX,
United Kingdom
Up to PL e,
category
4
only for models with integrated E-Stop button
UL
23
C (no direct sunlight)