Preparing Cables - Huawei LUNA2000 User Manual

Hide thumbs Also See for LUNA2000:
Table of Contents

Advertisement

LUNA2000-(5-30)-S0
User Manual

5.1 Preparing Cables

Figure 5-1 Battery cable connections
Table 5-1 Cables prepared by the customer
No.
1
2
3
Issue 01 (2020-10-20)
Cable
Type
DC input
Common outdoor
power cable
PV cable in the
industry
(inverter to
battery and
battery to
battery)
Signal cable
Outdoor shielded
(inverter to
twisted pair cable (8
battery and
cores)
battery to
battery)
Ground cable
Single-core outdoor
copper cable
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connection
Recommended
Specifications
● Conductor
cross-sectional
2
area: 4–6 mm
● Cable outer
diameter: 5.5–9
mm
● Conductor
cross-sectional
area: 0.20–0.35
2
mm
● Cable outer
diameter: 6.2–7
mm
2
● 10 mm
Source
Prepared
by the
customer
Prepared
by the
customer
Prepared
by the
customer
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents