Injecting Water to Expel Gas
To avoid blockage of the heat exchanger in the smart cooling product due to foreign matter
from the main pipe during the construction, you are advised to clean the main pipe before
water is supplied to the smart cooling product. Turn off the isolation valves on the water inlet
and outlet pipes before the cleaning and turn them on afterwards.
Open the exhaust valve of each heat exchanger to exhaust nitrogen onsite.
1. Open the general water supply valve.
2. Verify that the chilled water valve is open (100%). If not, press the button on the side of the
actuator, and manually rotate the valve handle to the maximum.
3. Slowly open the exhaust valve to discharge air.
4. Adjust the air exhausting speed until no air flows out of the valve. Then close the exhaust valve.
5. Manually close the chilled water valve.
4.7
Leakage Test with Water
If a leakage test with nitrogen has been performed, you do not need to perform a leakage test with
water.
1. Manually open the chilled water valve.
2. Raise the water pressure in the chilled water pipe to 0.8 MPa. If no leakage occurs after 30
minutes, retain the pressure for 24 hours. The expected result is that the pressure drop is less
than 0.01 MPa and the pipe does not leak.
3. Release the pressure in the pipes, and manually close the chilled water valve.
5

Connecting Cables

Cables must be routed in through cable clips. Strip the sheath of the power cable after routing the
cables into the electric control box.
Route and bind the cables along the beams and columns of the unit.
The cabinet has no input neutral wire. You can cut the blue neutral wire and wrap it using
insulation tape.