5.2 Network Drive Control Inputs and -Outputs

5.2.1 Analog Input- and Output Objects
Control the drive from the BACnet network using 'objects'. The various types of 'objects' and their descriptions are shown in the following tables.
Object ID
Object Name
Analog
AI:0
Input 53
Analog
AI:1
5
Input 54
Analog
AI:2
In X30/11
Analog
AI:3
In X30/12
Analog
AI:4
Input X42/1
Analog
AI:5
Input X42/3
Analog
AI:6
Input X42/5
Table 5.1: Analog inputs
Object ID
Object Name
Terminal
AO:0
42 Output Bus Control
Pulse out
AO:1
#27 Bus
Control
Pulse out
AO:2
#29 Bus
Control
Analogue
AO:3
Out X30/8 [mA]
Analogue
AO:4
output
X42/7[V]
Analogue
AO:5
output
X42/9[V]
Analogue
AO:6
output
X42/11[V]
Table 5.2: Analog outputs
20
Changeable
Non volatile ram
Read/Write
Description
Store
R
Yes
R
Yes
R
Yes
R
Yes
R
Yes
R
Yes
R
Yes
Changeable
Non volatile ram
Read/Write
Description
Store
W/R
Yes
W/R
Yes
W/R
Yes
W/R
Yes
W/R
Yes
W/R
Yes
W/R
Yes
Alarm
Drive Par.
notifi-
cation
No
DR-62
No
DR-64
No
DR-75
No
DR-76
No
LG-30
No
LG-31
No
LG-32
Alarm
Linked to AF-600
notifi-
FPParameter
cation
No
AN-53
No
E-93
No
E-95
No
AN-63
No
AO-43
No
AO-53
No
AO-63
AF-600FP BACnet
Triggers Bus time-
out
Yes
NO
Yes
NO
Yes
NO
Yes
NO
Yes
NO
Yes
NO
Yes
NO
Triggers Bus
Timeout
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes