Line-Side Power Components; General; Line Filters For Basic Line Modules; Description - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components

4.1

General

Line-side power components are used to protect the connected components against transient
or continuous overvoltages and ensure that prescribed limit values are adhered to.
4.2

Line filters for Basic Line Modules

4.2.1

Description

The line filters limit the conducted interference emitted by the Power Modules to permissible
values.
To reduce emissions, the Line Modules are equipped as standard with a line filter in
accordance with the limit values defined in category C3 (second environment). The additional
line filters described here is available for use in Category C2 (first and second environment).
In conjunction with line reactors, line filters limit the conducted interference emitted by the
Power Modules to the limit values defined in product standard EN 61800-3. Provided that the
system has been set up in accordance with the EMC installation guidelines, the limit values at
the installation location will be in accordance with the requirements for the first
environment.
The line filters are suitable for TN and TT supply systems grounded at the neutral point.
Table 4- 1
Assignment of line filter and Basic Line Module
Basic Line Module
6SL3330-1TE34-2AA3
6SL3330-1TE35-3AA3
6SL3330-1TE38-2AA3
6SL3330-1TE41-2AA3
6SL3330-1TE41-5AA3
6SL3330-1TE41-5AA3
6SL3330-1TE41-8AA3
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Rated power of the Basic Line Module
Line voltage 380 – 480 V 3 AC
200 kW
250 kW
400 kW
560 kW
710 kW
710 kW
900 kW
Suitable line filter
6SL3000-0BE34-4AA0
6SL3000-0BE36-0AA0
6SL3000-0BE41-2AA0
6SL3000-0BE41-2AA0
6SL3000-0BE41-6AA0
1)
6SL3760-0MR00-0AA0
2)
6SL3000-0BE41-6AA0
4