Instruction Manual Supplement
Instructions for UL and cUL have been revised.
Instructions for UL and cUL
(Standard to comply with: UL 508C, CSA C22.2 No. 14)
2. Installation
The below types of inverter have been approved as products for use in enclosure and approval
tests were conducted under the following conditions. Design the enclosure so that the surrounding
air temperature, humidity and ambience of the inverter will satisfy the above specifications.
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code for the U.S. or the
Canadian Electrical Code for Canada and any additional codes. As specified, UL Class T, Class J,
Class CC fuses or any faster acting fuse with the appropriate rating or Listed UL 489 Molded Case
Circuit Breaker (MCCB), or Type E combination motor controller must be employed.
FR-E720-(SC)-NA
Rated fuse voltage(V)
Without power
factor improving
Fuse allowable
reactor
rating (A)
With power factor
improving reactor
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)
Maximum
Type E
current rating (A)
combination
motor
Maximum
controller
SCCR (kA)
FR-E740-(SC)-NA
Rated fuse voltage(V)
Without power factor
improving reactor
Fuse allowable
rating (A)
With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
Maximum current
Type E
rating (A)
combination motor
Maximum SCCR
controller
(kA)
FR-E720S--NA
Rated fuse voltage(V)
Without power factor
improving reactor
Fuse allowable
rating (A)
With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
008
015 030 050 080
15
15
15
20
15
15
15
20
15
15
15
15
1.6
4
6.3
10
50
50
50
50
016 026 040
6
10
15
6
10
10
15
15
15
4
6.3
8
50
50
50
008 015 030
240V or more
15
20
20
15
20
20
15
15
15
1/2
110
175
240 330 470 600
240V or more
30
40
60
20
30
50
20
25
40
13
18
25
50
50
25
060 095 120 170 230 300
480V or more
20
30
40
70
15
25
35
60
15
20
30
40
10
18
25
32
50
50
25
25
050 080
110
30
40
60
20
30
50
20
25
40
BCN-C22005-792
70
80
150
175
60
70
125
150
60
80
110
150
80
90
70
90
50
70

Hide quick links: