Appendix: Tie Wrapping and Labeling
Tie Wrapping Requirements
The spacing between power cables, ground cables, and signaling cables must be larger than 30 mm.
Inside the cabinet, the cables must be tied neatly to form a rectangle cross section, and the cable ties must face the same direction.
Each bundle cannot have more than 20 cables. The cables must be tied every 200 mm and the cables must be fixed to the cabinet.
The cables must be labeled 20 mm away from both ends.
Cross section of the cable bundle
200mm
200mm
Cable manager
Labeling process
Fold to the right
Cross section of the cable bundle
1
Cable
Sticky side
Cables must be neatly tied.
Do not tie cables at bends.
Do not cut ties in a way
that creates pointed ends.
Cable manager
2
Cable
Fold upward
17

Label location

Ports
20mm
TO:
TO:
TO:
TO:
1 - A01 - 2 - A - 06
1 - A01 - 2 - A - 07
1 - A01 - 2 - A - 08
1 - A01 - 2 - A - 09
3
Cable
TO:
1 - A01 - 2 - A - 06