Appendix
Param-
Name
eter
Communication error
500
execution waiting time
Communication error
501
occurrence count display
Stop mode selection at
502
communication error
503
Maintenance timer 1
Maintenance timer 1
504
alarm output set time
505
Speed setting reference
S-pattern time at a start
516
of acceleration
S-pattern time at a
517
completion of
acceleration
S-pattern time at a start
518
of deceleration
S-pattern time at a
519
completion of
deceleration
522
Output stop frequency
Modbus-RTU
539
communication check
time interval
Frequency command
541
sign selection
Communication station
542
number (CC-Link)
Baud rate selection
543
(CC-Link)
544
CC-Link extended setting
USB communication
547
station number
USB communication
548
check time interval
549
Protocol selection
NET mode operation
550
command source
selection
PU mode operation
551
command source
selection
552
Frequency jump range
553
PID deviation limit
PID signal operation
554
selection
555
Current average time
556
Data output mask time
Current average value
557
monitor signal output
reference current
Second frequency search
560
gain
PTC thermistor
561
protection level
Frequency Inverters - Beginner's Guide
Setting Range
Initial Value
Parameter for communication
options FR-A8NC, FR-A8ND,
FR-A8NP
0–3
0
0 (1–9998)
0
0–9998, 9999
9999
1–590 Hz
60/50 Hz
0.1–2.5 s
0.1 s
0.1–2.5 s
0.1 s
0.1–2.5 s
0.1 s
0.1–2.5 s
0.1 s
0–590 Hz, 9999
9999
0–999.8 s,9999
9999
Parameter for communication
options FR-A8NC, FR-A8NCE,
FR-A8NP
Parameter for option FR-A8NC
(CC-Link communication)
0–31
0
0–999.8 s, 9999
9999
0, 1
0
0, 1, 9999
9999
1–3, 9999
9999
0–30 Hz, 9999
9999
0–100%, 9999
9999
0–3, 10–13
0
0.1–1.0 s
1 s
0–20 s
0 s
Rated
0–500A
/
inverter
0–3600A
current
0–32767, 9999
9999
0.5–30 kΩ, 9999
9999
Param-
Name
eter
Energization time
563
carrying-over times
Operating time carrying-
564
over times
Second motor speed
569
control gain
570
Multiple rating setting
571
Holding time at a start
4mA input check
573
selection
Second motor online
574
auto tuning
Output interruption
575
detection time
Output interruption
576
detection level
Output interruption
577
release level
Traverse function
592
selection
Maximum amplitude
593
amount
Amplitude
594
compensation amount
during deceleration
Amplitude
595
compensation amount
during acceleration
Amplitude acceleration
596
time
Amplitude deceleration
597
time
598
Undervoltage level
X10 terminal input
599
selection
First free thermal
600
reduction frequency 1
First free thermal
601
reduction ratio 1
First free thermal
602
reduction frequency 2
First free thermal
603
reduction ratio 2
First free thermal
604
reduction frequency 3
Motor permissible load
607
level
Second motor
608
permissible load level
PID set point/deviation
609
input selection
PID measured value
610
input selection
Parameter list (FR-A800)
Setting Range
Initial Value
(0–65535)
0
(0–65535)
0
0–200 %, 9999
9999
0–3/0–3/ 1, 2
2
0–10 s, 9999
9999
1–4, 9999
9999
0, 1
0
0–3600 s, 9999
1s
0–590 Hz
0 Hz
900–1100 %
1000 %
0–2
0
0–25 %
10 %
0–50 %
10 %
0–50 %
10 %
0.1–3600 s
5 s
0.1–3600 s
5 s
350–430 V, 9999
9999
0, 1
0/1/0
0–590 Hz, 9999
9999
1–100 %
100 %
0–590 Hz, 9999
9999
1–100 %
100 %
0–590 Hz, 9999
9999
110–250 %
150 %
110–250 %, 9999
9999
1–5
2
1–5
3
A - 9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820Fr-a840Fr-a842Fr-a846