Ambient conditions

1.2
Ambient conditions
Please observe the ambient conditions limits listed in the table below when operating the frequency
inverters described in this guide.
Specification
Surrounding
air
temperature
Ambient humidity for operation
and storage
Vibration
Installation environment
Installation altitude
Surrounding air temperature is a temperature measured at a measure-
ment position in an enclosure. Ambient temperature is a temperature
outside an enclosure.
The specific acceptable ambient temperature depends on the overload capacity of the individual inverter.
2.9 m/s
1 - 2
for operation
for storage
These temperatures are allowed for a short period only e.g. during shipping.
With circuit board coating, IP55 compatible models: 95% RH or less (non-condensing),
Indoors (free from corrosive or flammable gas, oil mist, dust and dirt)
Maximum 1000 m above sea level with no limitations. For altitudes above 1000 m derate
the inverter capacity by 3% for every additional 500 m.
Maximum installation altitude: 2500 m (with 91% of the inverter rated capacity)
2
or less for the FR-A840-04320(160K) or higher
FR-A800
FR-A820/A840/A842
−10 °C to 50 °C
−10 °C to 40
Non freezing
−20 °C to 65 °C
Without circuit board coating: 90% or less (non condensing)
5.9 m/s² (0.6 g) or less
Introduction
FR-A846
−10 °C to 40 °C
Enclosure
x = Measurement position
5 cm
5 cm
5 cm