ABB Relion 670 Series Product Manual page 76

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Bay control REC670
Version 2.2
Table 43. Thermal overload protection, one time constant LCPTTR/LFPTTR
Function
Reference current
Reference temperature
Operate time:
2
,
2
I
I
σ
<
p
t
ln
,
T
T
2
,
Trip
Amb
I
T
ref
EQUATION13000039 V3 EN-US
T
= set operate temperature
Trip
T
= ambient temperature
Amb
T
= temperature rise above ambient at I
ref
I
= reference load current
ref
I = actual measured current
I
= load current before overload occurs
p
Alarm temperature
Operate temperature
Reset level temperature
Table 44. Thermal overload protection, two time constants TRPTTR
Function
Base current 1 and 2
Operate time:
2
2
,
I
I
p
σ
< √
t
ln
2
2
,
I
I
Trip
(Equation 2)
EQUATION1356 V3 EN-US
I = actual measured current
Ip = load current before
overload occurs
ITrip = steady state operate
IBasex
current level in % of
Alarm level 1 and 2
Operate current
Reset level temperature
76
Range or value
(2-400)% of IBase
(0-300)°C, (0 - 600)°F
Time constant t = (1–1000)
minutes
2
I
ref
(Equation 1)
ref
(0-200)°C, (0-400)°F
(0-300)°C, (0-600)°F
(0-300)°C, (0-600)°F
Range or value
IBase
(30–250)% of
Time constant τ = (0.10–
500.00) minutes
(50–99)% of heat content
operate value
(50–250)% of
IBase
(10–95)% of heat content trip
© Copyright 2017 Hitachi Power Grids. All rights reserved
M12352-1 v15
Accuracy
±1.0% of I
r
±1.0°C, ±2.0°F
IEC 60255-149, ±5.0% or ±200 ms whichever is greater
±2.0°C, ±4.0°F
±2.0°C, ±4.0°F
±2.0°C, ±4.0°F
M13266-2 v9
Accuracy
±1.0% of I
r
±5.0% or ±200 ms whichever is greater
±2.0% of heat content trip
±1.0% of I
r
±2.0% of heat content trip
1MRK 511 404-BEN N
Hitachi Power Grids

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents