Bay control REC670
Version 2.2
Differential protection
Table 34. High impedance differential protection, single phase HZPDIF
Function
Operate voltage
Reset ratio
Maximum continuous power
Operate time at 0 to 10 x U
Reset time at 10 x U
to 0
d
Critical impulse time
Operate time at 0 to 2 x U
Reset time at 2 x U
to 0
d
Critical impulse time
1)
2
The value U
Trip/ R should always be lower than Stabilizing resistor thermal rating to allow continuous activation during testing. If this value is exceeded, testing should be
done with a transient faults. Typical value for the thermal rating of the resistor is 100W.
Hitachi Power Grids
Range or value
(10-900) V
I=U/R
>95% at (30-900) V
1)
See
Min. = 5 ms
d
Max. = 15 ms
Min. = 75 ms
Max. = 95 ms
2 ms typically at 0 to 10 x U
Min. = 25 ms
d
Max. = 35 ms
Min. = 50 ms
Max. = 70 ms
15 ms typically at 0 to 2 x U
© Copyright 2017 Hitachi Power Grids. All rights reserved
M13081-1 v13
Accuracy
±1.0% of I
at I ≤ I
r
±1.0% of I at I > I
-
-
-
d
-
d
1MRK 511 404-BEN N
r
r
67