Bay control REC670
Version 2.2
St and SimSt are supported as well as the
The attributes
SvCBRef , according to IEC 61850-7-4 Ed. 2.0.
setting
ALSVS is not defined in IEC 61850 Ed. 1
and is only supported in Ed. 2 mode.
IEC/UCA 61850-9-2LE communication protocol
Optical Ethernet port communication standard IEC/UCA
61850-9-2LE for process bus is supported. IEC/UCA
61850-9-2LE allows Non Conventional Instrument
Transformers (NCIT) with Merging Units (MUs) or stand-
alone MUs to exchange information with the IED, and
simplifies SA engineering. IEC/UCA 61850-9-2LE uses
the same port as IEC 61850-8-1.
LON communication protocol
Existing stations with ABB station bus LON can be
extended with use of the optical LON interface (glass or
plastic). This allows full SA functionality including peer-
to-peer messaging and cooperation between the IEDs.
SPA communication protocol
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation
automation systems but the main use is for Substation
Monitoring Systems SMS.
IEC 60870-5-103 communication protocol
A single glass or plastic port is provided for the IEC
60870-5-103 standard. This allows design of simple
substation automation systems including equipment
from different vendors. Disturbance files uploading is
provided.
Measurands for IEC 60870-5-103 I103MEAS
103MEAS is a function block that reports all valid
measuring types depending on the connected signals.
The set of connected inputs will control which ASDUs
(Application Service Data Units) are generated.
Measurands user-defined signals for IEC 60870-5-103
I103MEASUSR
I103MEASUSR is a function block with user-defined input
measurands in monitor direction. These function blocks
FunctionType parameter for each block in
include the
the private range, and the
parameter for each block.
Function status auto-recloser for IEC 60870-5-103 I103AR
I103AR is a function block with defined functions for
autorecloser indications in monitor direction. This block
FunctionType parameter, and the
includes the
information number parameter is defined for each
output signal.
48
GUID-C3AA21B4-730F-4327-943A-3C77102A80A0 v4
SEMOD120140-5 v3
SEMOD120134-5 v1
SEMOD120137-5 v4
Information number
© Copyright 2017 Hitachi Power Grids. All rights reserved
Function status earth-fault for IEC 60870-5-103 I103EF
I103EF is a function block with defined functions for
earth fault indications in monitor direction. This block
includes the
FunctionType parameter; the information
number parameter is defined for each output signal.
Function status fault protection for IEC 60870-5-103
I103FLTPROT
I103FLTPROT is used for fault indications in monitor
direction. Each input on the function block is specific for
a certain fault type and therefore must be connected to
a correspondent signal present in the configuration. For
example: 68_TRGEN represents the General Trip of the
device and must be connected to the general trip signal
SMPPTRC_TRIP or equivalent.
IED status for IEC 60870-5-103 I103IED
I103IED is a function block with defined IED functions in
monitor direction. This block uses the parameter
FunctionType ; the information number parameter is
defined for each input signal.
Supervison status for IEC 60870-5-103 I103SUPERV
I103SUPERV is a function block with defined functions
for supervision indications in monitor direction. This
FunctionType parameter; the
block includes the
information number parameter is defined for each
output signal.
Status for user-defined signals for IEC 60870-5-103
I103USRDEF
I103USRDEF comprises function blocks with user-
defined input signals in monitor direction. These
function blocks include the
each block in the private range, and the
number parameter for each input signal.
Function commands for IEC 60870-5-103 I103CMD
I103CMD is a command function block in control
direction with pre-defined output signals. The signals
are in steady state, not pulsed, and stored in the IED in
case of restart.
IED commands for IEC 60870-5-103 I103IEDCMD
I103IEDCMD is a command block in control direction
with defined IED functions. All outputs are pulsed and
they are NOT stored. Pulse-time is a hidden parameter.
Function commands user-defined for IEC 60870-5-103
I103USRCMD
I103USRCMD is a command block in control direction
with user-defined output signals. These function blocks
include the
FunctionType parameter for each block in
the private range, and the
parameter for each output signal.
1MRK 511 404-BEN N
FunctionType parameter for
information
Information number