PDU8000 Modular Precision PDC V2.0
User Manual
Alarm
Name
Branch
abnormal
Branch
overload
Max. br. cur.
exceed
Min. br. cur.
exceed
Main input
br. current
shock
Issue 03 (2018-01-25)
Alarm
Impact
Severity
Warning
A branch switch
is on, but no
current is
detected.
The current of a
Critical
branch exceeds 1
time of the rated
current (multiple:
1–1.2;
confirmation
time: 1–10s).
Major
The current of a
branch exceeds
0.8 time of the
rated current
(multiple: 0.8–1).
Warning
The current of a
branch exceeds
0.6 time of the
rated current
(multiple:
0.6–0.8;
confirmation
time: 1–10s).
Major
A surge current
three times
greater than the
rated current is
detected in a
branch (multiple:
1.5–5).
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance Guide
Possible
Solutions
Cause
No loading
If you do not to display
a Branch abnormal,
you set Branch
abnormal to Custom,
and set the branch to
Disable.
MDU path: System
Info. > Setting >
System Param.
The branch is
Check the load power
overloaded.
of the branch.
The branch is
Check the load power
overloaded.
of the branch.
N/A
N/A
The insulation
Check the cable
of the branch
insulation of the output
is abnormal.
branch.
123