X9 Terminal Strip; Dcps, Dcns Connection For A Dv/Dt Filter - Siemens SINAMICS S120 Equipment Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

6.3.4

X9 terminal strip

Table 6- 3
Max. connectable cross-section:
- terminal 1 ... 6: 2.5 mm
- terminals L1, L2: 35 mm
Note
Connecting the fan supply with frame sizes FX and GX
The fan supply for frame sizes FX and GX is connected directly to fuse holders -F10 and
-F11.
6.3.5

DCPS, DCNS connection for a dv/dt filter

Table 6- 4
With frame sizes FX and GX, the connecting cables are routed down through the Motor Module and
out.
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
Terminal strip X9
Terminal
Signal name
1
P24V
2
M
3
VL1
4
VL2
5
HS1
6
HS2
L1
Connection for fan
supply
L2
(frame sizes HX and JX
only)
2
2
DCPS, DCNS
Frame size
FX
GX
HX
JX
Technical specifications
External 24 V DC supply
Voltage: 24 VDC (20.4 ... 28.8 V)
Current consumption: max. 1.4 A
240 V AC: 8 A max.
24 VDC: max. 1 A
isolated
240 V AC: 8 A max.
24 VDC: max. 1 A
isolated
380 ... 480 VAC / 500 ... 690 VAC
Current consumption: See Technical data
Connectable cross-section
1 x 35 mm²
1 x 70 mm²
1 x 185 mm²
2 x 185 mm²
Motor Modules
6.3 Interface description
Terminal screw
M8
M8
M10
M10
259

Advertisement

Table of Contents
loading

Table of Contents