Huawei UPS5000-E-50K-HABBS Quick Manual

Hide thumbs Also See for UPS5000-E-50K-HABBS:

Advertisement

Quick Links

UPS5000-E-(60 kVA–125 kVA)
Quick Guide (Integrated UPS 3.0)
Issue: 01
Part Number: 31500DXL
Date: 2020-04-13
1
Overview
UPS Model
UPS5000-E-50K-HABBS
UPS5000-E-50K-HASBS
UPS5000-E-125K-HABBS-01
UPS5000-E-125K-HASBS-01
The appearance of the UPS5000-E-60K-HABBS (02312TVW, 02312TWB) is similar to that of
the UPS5000-E-125K-HABBS-01 (02312TVY, 02312TWC).
The appearance of the UPS5000-E-60K-HASBS (02312TVX) is similar to that of the UPS5000-
E-125K-HASBS-01 (02312TWA).
If Requisite modules is set to 5, the maximum output capability of each module is 25 kVA/25 kW.
1. Before installation, read the user manual carefully to get familiar with product information and
safety precautions.
2. Use insulated tools during installation.
3. Only engineers certified by Huawei or its agents are allowed to install, commission, and
maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS
faults caused are beyond the warranty scope of Huawei.
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
Capacity
Weight (Full
Configuration
Configuration)
352 kg
30 kVA, 60 kVA
390 kg
435 kg
90kVA, 120kVA,
125kVA
453 kg
1
Dimensions (H x W x D)
2000 mm x 600 mm x
1100 mm

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-E-50K-HABBS

  • Page 1 2. Use insulated tools during installation. 3. Only engineers certified by Huawei or its agents are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS faults caused are beyond the warranty scope of Huawei.
  • Page 2 UPS5000-E-60K-HABBS (1) Power input (2) Input circuit status indicator breaker (4) Power distribution (3) Lighting circuit breaker for the circuit breaker mart cooling product (5) IT load circuit (6) UPS input breaker circuit breaker (7) UPS maintenance (8) Control module bypass circuit breaker (9) Bypass module (10) Filler panel...
  • Page 3: Installing The Ups

    Installing the UPS 1. Determine the mounting holes based on the marking-off template, drill holes, and install expansion sleeves (unit: mm). 2. Adjust the anchor bolts and ensure that the 3. Secure the UPS. anchor bolts touch the floor. Then level the UPS.
  • Page 4 (Optional) Installing the Tail Frame 1. Secure the tail frame fittings to the tail frame. 2. Secure the tail frame upper sealing plate to the tail frame. There are two upper sealing plates, and the one used in this step has a gap. 3.
  • Page 5: Connecting Cables

    1. Open the front and rear doors. Wrench the 2. Remove the cabinet connecting kits from anchor bolts using an wrench to adjust the the rack. cabinet height. Use a level to level the cabinet. 3. Secure the connecting kits in the connection positions on the front door using screws.
  • Page 6 Connecting Power Cables The cabling route is for reference only. Connect cables based on site requirements. Scenario 1: Routing Cables from the Top 1. Remove the insulation protective panel from 2. Connect a ground cable to the UPS cabinet. the rear of the cabinet and remove covers from the top as required.
  • Page 7 4. Connect battery cables, AC output power cables, fire protection cables and generator Start/Stop cables. Neutral cables PE cables IT and smart cooling product output power Battery cables cables Lighting cables Fire Protection and Generator Start/Stop Cables (ATS input cabinet) Route a neutral wire from the middle of the positive and negative battery strings.
  • Page 8 Scenario 2: Routing Cables from the Bottom • Cables can be routed in and out from the bottom only when a tail frame is configured for the cabinet. • This section uses the ATS cabinet as an example. For details about cable connections in other cabinets, see the procedure in this section.
  • Page 9 5. Connect the battery cable and ground cable 6. Connect AC output power cables. of the cabinet. Lighting wiring terminal Smart cooling product wiring terminal IT wiring terminal Connecting Communications Cables Connecting Communications Cables to Northbound Devices Connect a communications cable between the FE port on the UPS monitoring interface card and any PoE port on the ETH gateway.
  • Page 10: Verifying The Installation

    (Optional) Connecting SmartLi Communications Cables Connect one end of the cable to the COM1 port on the UPS monitoring interface card, and connect the other end to the COM port on the SmartLi monitoring interface unit. ETH gateway Verifying the Installation 1.
  • Page 11 (Optional) ATS Commissioning Before System Power-On Perform system commissioning and power-on strictly according to the system manual and ATS instructions. For any changes in operations and parameters, consult Huawei engineers. Otherwise, system commissioning or power-on may fail, or even the cabinet is damaged.
  • Page 12 (1) OTM_C8D (2) Motor/Manual controller (8D selection lever controller for short) (3) Motor operator (4) Handle locking latch (5) Manual handle (6) Handle buckle (7) Position for (8) Transfer switch auxiliary contacts (10) Alarm ID (9) Operator description 1. Switch on the power switch for the ATS electric operation mechanism (Q1 and Q2 in the lower left side at the rear of the cabinet) to power the ATS electric operation mechanism.
  • Page 13 5. Modify configurations of the 8D controller. 1. You are not allowed to modify the ATS configurations if not authorized by Huawei engineers. 2. When the controller is in button mode, do not simultaneously press and hold down the I, II, and O buttons on the controller panel.
  • Page 14: Powering On And Starting The Ups

    7 "ATS Commissioning input used? Before System Power-On". Switch on the MCCB. Switch on the UPS input circuit breaker QF1. The UPS works in normal mode and starts initialization. The LCD displays the Huawei logo and an initialization progress bar.
  • Page 15 Initial Startup • If the UPS is powered on for the first time, you need to obtain the startup password from the Service Expert app. Skip this step if the UPS is not powered on for the first time. • The Service Expert app can be downloaded from Google Play Store and can run on Android.
  • Page 16 2. Set the language, time, date, network parameters, and system parameters on the Settings Wizard screen.
  • Page 17 3. After you perform the settings, the Bypass mode and No battery alarms are reported by the MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault . 4. (Optional) Set ATS parameters. 5.
  • Page 18: Shutting Down The Ups

    Shutting Down the UPS After you shut down the inverter, the UPS transfers to bypass mode if the bypass is normal; the UPS supplies no power if the bypass is abnormal. Before shutting down the UPS, ensure that all loads have been shut down. Shutting Down the Inverter to Transfer the UPS to Bypass Mode 1.
  • Page 19 Common Alarms and Troubleshooting Measures Alarm Possible Cause Troubleshooting Measures Mains ph. The mains input phase sequence Verify that the mains input phase sequence is reversed is reversed. correct using a phase sequence meter. Bypass ph. The bypass input phase Verify that the bypass input phase sequence is reversed sequence is reversed.
  • Page 20 Scan here for technical support (carrier): Huawei App Store Scan here for more documents: Support-E Support WeChat You can also log in to Huawei technical support website: https://support.huawei.com/enterprise https://support.huawei.com Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China...