UPS5000-E-600K-FMS UPS5000-E-600K-FMS-01 (1) Power modules (2) Control module (3) Power distribution module covers (4) Maintenance bypass switch (5) Bypass module (6) Main input switch (7) Output switch (8) Bypass input switch UPS5000-E-400K-SMS, UPS5000-E-500K-SMS, and UPS5000-E-600K-F600-SMS, UPS5000-E- 400K-SMS-01, UPS5000-E-500K-SMS-01, UPS5000-E-600K-SMS-01 are models in standard configuration.
Page 3
A: Mounting holes on the channel steel B: Mounting holes on the floor 400/500K Hole Dimensions Unit: mm 600K Hole Dimensions Unit: mm...
Securing the UPS Floor mounting: Secure the cabinet to the floor by using eight M12x60 expansion bolts. • • Channel steel mounting: Secure the cabinet to channel steel by using eight M12x60 common bolts. (1) Cabinet mounting holes (floor mounting mode) (2) Cabinet mounting holes (channel steel mounting mode) Installing the Front, Rear, Left, and Right Anchor Baffle Plates Installing Cables...
Page 5
Scenario 1: Routing Cables from the Top 2. Remove the top cover from the 1. Open the front door of the bypass cabinet based on cable routes and cabinet, and remove power distribution dimensions. covers (UPS5000-E-400K-FMS is used as an example).
Page 6
3. Remove the copper bar between the mains 4. Connect the ground cable to the UPS. and bypass inputs. (Skip this step if there is only one power source.) 5. Connect the mains input power cable. 6. Connect the output power cable.
Page 7
8. Connect the battery cable. 7. Connect the bypass input power cable. 9. Connect signal cables. Route a neutral wire from the middle of the positive and negative battery strings. Take a battery string consisting of 40 batteries as an example. A neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries.
Scenario 2: Routing Cables from the Bottom 1. Remove the cable covers from the bottom of the cabinet, drill holes in the covers, attach grommet strips to the hole edges for protecting cables, and reinstall the cable covers. 2. Connect power cables and signal cables. For the screw specifications and torque used for connecting cables in a bottom cable routing scenario, refer to the top cable routing scenario.
2. After routing cables and checking cable connections, use sealing putty to fill in the gap between the cables and the cabinets. (Remove the paper protective film from the sealing putty and retain the transparent film. When using the putty, ensure that the transparent film faces upward.) Paper Transparent film...
If the UPS is powered on for the first time, you need to obtain the startup password from the Service Expert app. Skip this step if the UPS is not powered on for the first time. The Service Expert app can be downloaded from HUAWEI AppGallery and can only run on •...
Page 11
2. Set the language, time, date, network parameters, system parameters, and battery parameters on the Settings Wizard screen. 3. After you perform the settings, the Bypass mode and No battery alarms are reported by the MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault. 4.