Huawei UPS5000-E Series User Manual

Huawei UPS5000-E Series User Manual

Integrated ups, 50/125 kva
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS
3.0)
Issue
09
Date
2019-12-20
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-E Series

  • Page 1 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) Issue Date 2019-12-20 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Updated the section "Technical Specifications". Issue 03 (2018-01-15) Updated the Monitoring screen image. Issue 02 (2017-11-27) Updated the section "Technical Specifications". Issue 01 (2017-08-30) This issue is the first official release. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    2.3.4.1 Overview ................................27 2.3.4.2 ECM................................27 2.3.4.3 Dry Contact Card ............................29 2.3.4.4 Monitoring Interface Card ..........................30 2.3.5 MDU .................................35 2.4 02311FTE-002 and 02311FTC-001 Automatic Transfer Switch (ATS) ..............37 2.4.1 ATS Appearance ..............................37 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 6 3.4.2 Connecting Signal Cables ..........................95 3.5 Installation Verification ............................95 4 User Interface .......................... 98 4.1 LCD Interface ..............................98 4.1.1 LCD Menu ................................98 4.1.1.1 Menu Hierarchy ..............................98 4.1.1.2 Initial Startup ..............................98 4.1.1.3 Main Menu ..............................99 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 5.7 Transferring to Bypass Mode ..........................177 5.8 Setting ECO Mode ............................. 178 5.9 Testing Batteries ..............................180 5.9.1 Forced Equalized Charging Test ........................180 5.9.2 Shallow Discharge Test ............................ 180 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 8 8.3 Replacing a Circuit Breaker ..........................217 8.4 Replacing an ATS ............................... 218 9 Technical Specification ....................... 223 A Menu Hierarchy ........................226 A.1 Menus on the LCD ............................226 A.2 Menus on the WebUI ............................228 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 9 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) Contents B PDC Silk Screen Description ..................... 232 C Alarm List ..........................233 D Acronyms and Abbreviations.................... 243 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd. viii...
  • Page 10: Safety Information

    The "NOTICE", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
  • Page 11  Keep irrelevant people away from the equipment. Only operators are allowed to access the equipment.  Use insulated tools or tools with insulated handles, as shown in the following figure. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 12  To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to telecommunication network voltage (TNV) circuits. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 13: Personnel Requirements

    Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements  Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations.
  • Page 14 When selecting, connecting, and routing cables, follow local safety regulations and rules. The static electricity generated by human bodies may damage the electrostatic-sensitive components on boards, for example, the large-scale integrated (LSI) circuits. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 15: Installation Environment Requirements

     Ensure that the equipment room provides good heat insulation, and the walls and floor are dampproof.  Install a rat guard at the door of the equipment room. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 16: Mechanical Safety

    Before hoisting objects, ensure that hoisting tools are firmly secured onto a load-bearing object or wall.  Ensure that the angle formed by two hoisting cables is no more than 90 degrees, as shown in the following figure. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 17 Do not climb higher than the fourth rung of the ladder from the top.  Ensure that your body's center of gravity does not shift outside the legs of the ladder. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Device Running Safety

    Metal shavings from drilling may short-circuit boards inside the equipment.  Obtain the consent from the customer, subcontractor, and Huawei before drilling.  Wear goggles and protective gloves when drilling holes. ...
  • Page 19 The UPS can be configured with a backfeed protection dry contact to work with an external automatic circuit breaker, preventing the voltage from flowing back to input terminals over static bypass circuits. If the installation and maintenance personnel do not need backfeed Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Battery Safety

     Dispose of waste batteries in accordance with local laws and regulations. Do not dispose of batteries as household waste. If a battery is disposed of improperly, it may explode. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 21 The site must be equipped with qualified fire extinguishing facilities, such as firefighting sands and powder fire extinguishers. To ensure battery safety and battery management accuracy, use batteries provided with the UPS by Huawei. Huawei is not responsible for any battery faults caused by batteries not provided by Huawei. Battery Installation Before installing batteries, observe the following safety precautions: ...
  • Page 22: Others

    Exercise caution when manually shutting down the UPS inverter for transferring to bypass mode, or when adjusting the UPS output voltage level or frequency. Doing so may affect the power supply to equipment. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 23 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 1 Safety Information  Exercise caution when setting battery parameters. Incorrect settings will affect the power supply and battery lifespan. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 24: Overview

    A: air cooled type Input switch type B: MCCB S: ATS Output type B: branch power distribution Configuration type S: standard configuration This document describes the following UPS models:  UPS5000-E-50K-HABBS Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Working Principle

    Its power module consists of a rectifier and inverter. The UPS5000 converts inputs into pure, high-quality sine wave outputs by using the high-frequency switching technology. Figure 2-2 Conceptual diagram in air cooled scenario Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Working Modes

    The bypass power supply is not protected by the UPS which means it may be affected by mains outage, and incorrect AC voltage or frequency. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Battery Mode

    If the mains input is abnormal or the rectifier becomes abnormal, the UPS transfers to battery mode. The power module obtains DC power from batteries, and the power is converted into AC output by the inverter. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Maintenance Bypass Mode

    2.2.2.4 Maintenance Bypass Mode When the UPS works in maintenance bypass mode, the current flows through the maintenance bypass instead of the power module. You can maintain the circuit inside the cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 29: Eco Mode

    ECO voltage range, the UPS transfers from bypass mode to normal mode. In bypass mode or normal mode, the rectifier keeps working and charges batteries using a charger. The ECO mode delivers a high efficiency. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Product Introduction

    The appearance of the UPS5000-E-125K-HASBS (02311FTE-002) is similar to that of the UPS5000-E-50K-HASBS (02311FTC-001).  The appearance of the UPS5000-E-125K-HASBS (02311FTE-004, 02311FTE-006) is similar to that of the UPS5000-E-50K-HASBS (02311FTC-004, 02311FTC-006). Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 31 (7) UPS maintenance bypass circuit (8) Control module (9) Bypass module breaker (10) Filler panel (11) Power module (12) Monitor display unit (MDU) (13) Power distribution monitoring board (14) UPS output circuit breaker Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 32 (8) UPS maintenance bypass circuit (9) Control module breaker breaker (10) Bypass module (11) Power module (12) Monitor display unit (MDU) (13) Power distribution (14) UPS output circuit breaker monitoring board Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 33 (10) Bypass module (11) Power module (12) ATS transfer switch (13) ATS handle (14) Monitor display unit (MDU) (15) Power distribution monitoring board (16) UPS output circuit breaker Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 34: Power Module

    Dimensions (H x W x D): 86 mm x 442 mm x 620 mm  Weight: < 21 kg  Rated output capacity: 25 kVA/25 kW  Power density: 17.2 W/inch Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 35: Bypass Module

    The UPS is set to ECO mode and the bypass voltage is within the specified range. The power module is overloaded for a period longer than the maximum allowed period. Both the active and standby ECMs are abnormal. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 36: Control Module

    The control module consists of two ECMs that work in active/standby mode. Each card provides two ports, that is, a BSC port in the upper part and a reserved parallel port in the lower part. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 37 The ECM has no minor alarm or the DSP of the ECM is being upgraded. FAULT Steady on The ECM has a critical alarm. The ECM has no critical alarm or the DSP of the ECM is being upgraded. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 38: Dry Contact Card

    BCB_0V Port for signal ground EPO_NO Emergency power-off If the normally open Disconnected (EPO) port (NO) port is connected to the EPO_12V +12 V EPO_12V port, EPO Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 39: Monitoring Interface Card

    Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m, its cross-sectional area must be 0.5 mm to 1.5 mm 2.3.4.4 Monitoring Interface Card Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 40 DO_3 DO_3 is used to output alarms and indicates bypass mode by default. It can be set to indicate critical alarms, minor alarms, battery mode, or low battery Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 41 0.5–1.5 mm  RS485 cables and FE cables must be shielded cables. Figure 2-17 Figure 2-18 are recommended wiring methods for DO ports. Figure 2-17 Wiring method 1 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 42 Figure 2-19 Table 2-6 describe the COM1 pin definitions. Figure 2-19 COM1 pins Table 2-6 COM1 pin definition Description RS485- RS485+ 12V_PORT Figure 2-20 Table 2-7 describe the COM2 pin definitions. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 43 2 Overview Figure 2-20 COM2 pins Table 2-7 COM2 pin definition Description RS485+ RS485- RS485+ RS485- CANH0 CANL0 Figure 2-21 Table 2-8 describe the RS485 pin definitions. Figure 2-21 RS485 pins Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 44: Mdu

    RS485+. Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485–. 2.3.5 MDU Appearance Figure 2-22 MDU (1) Status indicator (2) LCD touchscreen Table 2-9 Status indicator Status Color Meaning Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 45 Insert the USB flash drive, import and export the configuration file, export run logs, and upgrade software. Restart switch for the MDU Reserved DIP switch Implements specific functions by using the DIP switch and Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 46: 02311Fte-002 And 02311Ftc-001 Automatic Transfer Switch (Ats)

    (1) Controller (2) Electric/Manual mode (3) Electric operating selection handle mechanism (4) Handle locking latch (5) Manual handle (6) Handle buckle (7) Position for auxiliary (8) Transfer switch (9) Operating mechanism Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 47: Ats Controller

    Before you pull out the handle, turn the handle locking latch downwards. After you pull out the handle, flip the electric/manual mode selection handle upwards to the M position. 2.4.2 ATS Controller Figure 2-25 shows an ATS controller. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 48 Incorrect The phase sequence of the power supply is incorrect. phase sequence Invalid The supply frequency exceeds the threshold. frequency Table 2-12 describes the buttons on the ATS controller. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 49 On: The ATS is powered on.  Blinking: The ATS is in standby mode.  Off: The ATS is powered off. The controller is in standby state for at least 1 minute. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 50 If LN1 and LN2 power indicators are hollow, there is an alarm. Locate the fault based on the alarm ID Table 2-11 or the alarm ID description on the 8D controller, and rectify the fault. Figure 2-27 Generator status Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 51 Note that the LLVD status (ON/OFF) in the menu is consistent with the input data. For example: If the input data (DI 11 by default) is active, the LLVD is on. If the input data is invalid, the LLVD is off. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Ats (8D) Operation Description

    Step 3 Press down the locking latch on the switch panel and pull out the handle. Figure 2-30 Pulling out the handle If the handle is not pulled out, the automatic mode will be disabled. Step 4 Flip the Motor/Manual selection lever to the Motor position. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 53 ATS operation mechanism. Step 2 Check whether the 8D controller has alarms. If an alarm exists, rectify the fault first. Step 3 Flip the Motor/Manual selection lever to the Man. position. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 54 The automatic operation will be disabled after the handle is inserted into the switch panel. Step 5 The Alarm LED and Power LED indicators go on at the same time when the handle is inserted. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 55 Step 2 Check whether the 8D controller has alarms. If an alarm exists, rectify the fault first. Step 3 Press down the locking latch on the switch panel and pull out the handle. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 56 If the Auto LED indicator is on, press the Auto button once. Then the Auto LED indicator turns off, and the controller enters the button mode, as shown by (2) in Figure 2-38. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 57: 02311Fte-004, 02311Fte-006, 02311Ftc-006 And 02311Ftc-004 Automatic Transfer Switch (Ats)

    ATS operating  Steady green: indicates that the ATS is status indicator operating properly.  Steady yellow: indicates a warning and minor alarm.  Steady red: indicates a critical or major alarm. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 58: Ats Iii Segment Manual Operation Description

    Ensure that the primary and secondary contacts of the ATS work smoothly.  Verify that the phase sequences of the two power inputs to the ATS are correct using a phase sequence table. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 59 Step 1 Check whether the ATS monitoring module has alarms. If an alarm exists, rectify the fault first. Step 2 Insert the handle into the switch panel. Turn the handle clockwise in the direction of the arrow until the I sign indicates I (ON). Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 60 II sign indicates II (ON). Figure 2-42 Inserting and rotating the handle Step 3 Place the handle back to the original position. ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 61: Optional Components

    UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 2 Overview 2.6 Optional Components Table 2-15 Optional components Component Model Function 5m/10m/15m/60m Transmits bus synchronization signals in a dual-bus system. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 62: Installation

    Electric pallet truck Manual pallet truck Ladder Rubber mallet Hammer drill and Hand-held electric Alloy hole saw Heat gun drill bit Φ16 drill Diagonal pliers Crimping tools Wire stripper Electric hydraulic pliers Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 63 Protective gloves Insulated gloves Insulation protective discharge (ESD) shoes gloves Torque screwdriver Cable cutter Brush Flat-head screwdriver (2–5 mm) Phillips screwdriver Insulated torque Heat shrink tubing Insulated adjustable wrench wrench (M3/M4/M5/M6/M (M6/M8/M12/M16) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 64: Site

    3.1.2 Site 3.1.2.1 UPS Weight and Dimensions Table 3-2 Weight Model Number of Number of Weight Modules Redundant Modules UPS5000-E-50K-HABBS 352 kg UPS5000-E-50K-HASBS 390 kg UPS5000-E-125K-HABBS 435 kg UPS5000-E-125K-HASBS 453 kg Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 65 User Manual (Integrated UPS 3.0) 3 Installation Figure 3-1 Dimensions (unit: mm) (1) Front door (2) Foot (3) Caster (4) Bottom plate (5) Rear door (6) Base mounting hole (7) Side post (8) Beam Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 66: Installation Environment

    Reserve a clearance of at least 800 mm from the rear of the cabinet.  Reserve a clearance of at least 500 mm from the top of the cabinet. Figure 3-2 Reserved clearances (unit: mm) 3.1.3 Preparing Power Cables Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 67 2 x 95 2 x 95 2 x 95 2 x 95 Table 3-4 Recommended cross-sectional areas for output cables Item Cable Specifications Air conditioner (40 A) 5 x 6 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 68 Single- or multi-core 90° C soft power cables with copper conductors are used.  It is recommended that AC power cables be no longer than 30 m and DC power cables be no longer than 40 m. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 69: Unpacking And Checking

     Check that the fittings comply with the packing list. If some fittings are missing or do not comply with the packing list, record the information and contact your local Huawei office immediately.  If the UPS installation environment is in poor condition and the UPS will be stored for a long time after it is unpacked, wrap the UPS with the original plastic coat to prevent dust.
  • Page 70 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 3 Installation Figure 3-3 Removing the L-shaped bracket Step 4 Insert the two sliding plates under the pallet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 71 Step 5 Raise the four anchor bolts to the highest position using an adjustable wrench. Figure 3-5 Raising the leveling feet Step 6 Move the UPS over its castors near the installation position. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 72: Installing A Single Ups

    Step 1 Determine the position for installing the cabinet. Mark mounting holes based on the drawings or marking-off template. Figure 3-6 Mounting holes (unit: mm) Step 2 Use a hammer drill to drill holes for installing expansion bolts and then install expansion bolts in the holes. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 73 Partially tighten the expansion bolt and vertically insert it into the hole. Knock the expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the hole. Partially tighten the expansion bolt. Remove the bolt, spring washer, and flat washer. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 74 4. Do not remove anchor bolts. Otherwise, you need to rework them for use. Step 2 Check the cabinet levelness using a level. If the cabinet is not leveled, adjust the anchor bolts. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 75 Do not remove anchor bolts. Otherwise, you need to rework them for use. Step 3 Insert four M12 bolt assemblies into the mounting holes for the UPS and support. Partially tighten the bolts. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 76: Installing A Tail Frame

    A tail frame is used to increase the depth of a UPS to 1200 mm, and can also be used to route cables in and out from the bottom. Its BOM number is 21242025. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 77 User Manual (Integrated UPS 3.0) 3 Installation Figure 3-12 Installed tail frame (1) Tail frame Procedure Step 1 Use eight M5 tapping screws to secure the tail frame accessories to the tail frame. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 78 Step 2 Use four M5 tapping screws to secure one upper sealing plate to the tail frame. There are two upper sealing plates, and the one used in this step has a gap. Figure 3-14 Upper sealing plate Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 79 Figure 3-15 Securing the upper sealing plate Step 3 Open the UPS rear door, and remove it. When removing the cabinet rear door, remove the ground cable between the cabinet and the rear door from the cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 80 Step 4 Remove the hinges and connecting kits from the UPS rear door and remove the ground cable. Put aside the hinges and connecting kits as they are needed in follow-up installation processes. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 81 Step 5 Move the tail frame to the cabinet rear door, and adjust the tail frame so that the tail frame top is flush with the cabinet top. Step 6 Secure the tail frame to the UPS using eight M5 tapping screws. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 82 Figure 3-18 Securing the tail frame Step 7 Install the hinges and connecting kits removed in Step 4 at the corresponding positions on the tail frame. Step 8 Install fixing plates for cable ties. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 83: Installing Batteries

    Step 9 Install the UPS rear door on the tail frame. After installing the UPS rear door, ensure that ground cables are properly connected to the cabinet and UPS rear door. ----End 3.2.3 Installing Batteries Context Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 84: Routing At The Top

    Step 1 Remove five rodent-proof meshes and cable hole protection panels from the top of the cabinet. You can drill holes in the removed covers as required before reinstalling them on the cabinet. Figure 3-20 Removing rodent-proof meshes Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 85 User Manual (Integrated UPS 3.0) 3 Installation Figure 3-21 Removing cable hole protection panels Step 2 Open the rear door, and remove the insulation panels at the rear of the cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 86 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 3 Installation Figure 3-22 Removing insulation covers Step 3 Route power cables. Step 4 Route signal cables. Bind cables to the cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 87: Connecting A Ground Cable

    Prepare terminals onsite. The length of the copper wire should be the same as that of the part of the terminal that covers the conductor. Procedure Step 1 Connect a ground cable to the UPS cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 88: Connecting Ac Input Power Cables

    3.2.4.3 Connecting AC Input Power Cables 02311FTE-002 and 02311FTC-001 Cabinet Input Step 1 Connect two AC input power cables to input terminals 1L1, 1L2, 1L3, 1N and 2L1, 2L2, 2L3, 2N on the UPS cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 89 ----End 02311FTE-004 and 02311FTE-006 Cabinet Input Step 1 Connect two AC input power cables to input terminals 1L1, 1L2, 1L3, 1N and 2L1, 2L2, 2L3, 2N respectively on the UPS cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 90 Figure 3-29 Input terminals ----End 02311FTD-002, 02311FTD-007, 02311FTB-001 and 02311FTB-009 Cabinet Input Step 1 Connect AC input power cables to input terminals L1, L2, L3, and N on the UPS cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 91: Connecting Ac Output Power Cables

    Connect output power cables to the customer terminal bars in the UPS cabinet, and connect N cables and PE cables to the N bar and PE bar on the left and right sides. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 92 Figure 3-31 Connecting output power cables to customer terminals (1) IT and air conditioner output power cables (2) Lighting output power cables Figure 3-32 Output N cables and PE cables (1) Neutral cables (2) PE cables Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 93: Connecting Battery Cables

    Step 2 Route a neutral wire from the middle connection point of positive and negative battery strings. Take a battery string consisting of 32 batteries as an example. The neutral wire routed from the middle of positive and negative battery strings, each consisting of 16 batteries. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 94: Routing At The Bottom

    Step 1 Remove the cover plate from the cable hole at the bottom of the tail frame. Step 2 Remove the insulation panels at the rear of the cabinet. Step 3 Connect a ground cable to the safety ground of the UPS cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 95 Step 4 Connect two AC input power cables to input terminals 1L1, 1L2, 1L3, 1N and 2L1, 2L2, 2L3, 2N on the UPS cabinet. Connect the inside cables first, and then the outside cables. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 96 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 3 Installation Figure 3-36 Input power cable Step 5 Connect the battery cable and ground cable of the cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 97 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 3 Installation Figure 3-37 Battery cable and ground cable Step 6 Connect the output power cables. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 98: Connecting Signal Cables

    3.2.6 Connecting Signal Cables 3.2.6.1 Connecting a Remote EPO Switch  Huawei does not provide an EPO switch and cable. Prepare them before installation. The 22 AWG cable is recommended. AWG is short for American wire gauge.  To prevent problems, equip the EPO switch with a protective cover, and enclose the cable with a protective tube.
  • Page 99: Connecting Communications Cables

    Step 1 Connect one end of the cable to the FE port on the UPS monitoring interface card, and connect the other end to any PoE port on the smart ETH gateway. Figure 3-41 Connecting Communications Cables ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 100: Connecting Fire Protection And Generator Start/Stop Cables (Ats Input Cabinet)

    Here connecting one of the cables is used as an example. XT2-6 is a normally open contact, XT2-7 is a common contact, and XT2-8 is a normally closed contact. Figure 3-42 Connecting the fire protection and generator start/stop cables for the UPS (1) XT2 terminal block Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 101: Optional) Combining Cabinets

    Step 2 Remove the cabinet connecting kits from the rack, as shown in Figure 3-44. Step 3 Secure the connecting kits in the connection positions on the front door using screws, as shown in Figure 3-44. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 102: Installing A Double-Bus (2N) System

    Step 1 Ground each single UPS. Step 2 Connect AC input and output power cables of each UPS. Step 3 Connect battery power cables of each UPS. Step 4 Connect cables to the dual-bus system. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 103 User Manual (Integrated UPS 3.0) 3 Installation Figure 3-45 Conceptual diagram of a dual-bus system Figure 3-46 Cable connections to a dual-bus system (1) Input power cables (2) Battery cables (3) Output power cables ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 104: Connecting Signal Cables

    Ensure that there is no disconnection or potential risk. Serial port connection (security Signal cables are connected properly and protection mechanism securely. supported) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 105 3. There is no foreign matter around switch terminals. 4. There is no foreign matter on the bottom plate of the cabinet. 5. There is no foreign matter on the rear module subrack. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 106  After verifying the installation, reinstall all the covers.  Do not remove the dustproof cover before power-on to prevent dust inside the UPS. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 107: User Interface

    4.1 LCD Interface 4.1.1 LCD Menu 4.1.1.1 Menu Hierarchy Figure 4-1 Menu hierarchy 4.1.1.2 Initial Startup User interfaces displayed in this document correspond to the software version V100R003C01SPC474 and are for reference only. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 108: Main Menu

    Param., and System Param. on the Settings Wizard screen. Figure 4-2 Settings Wizard 4.1.1.3 Main Menu The LCD screen is divided into three parts: status bar, alarm bar and information area. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 109 Table 4-2 Functions of common buttons Button Function Returns to the main screen. Goes to the lower part of a page. Goes to the upper part of a page. Returns to the upper-level menu. Logs out. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 110: System Info Screen

    If Cross current monitoring is set to Enable on the System Info > Settings > Advanced Param. screen and the number of modules in inverter mode is greater than 1, Mod. Cur. Eql. Data is displayed on the running screen. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 111 User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-6 Runn Info screen 1 Figure 4-7 Runn Info screen 2 AC Output Figure 4-8 AC output  Phase voltage (V)/Line voltage (V)/Phase current (A)/Frequency (Hz) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 112 Load ratio of each phase on the UPS, that is, proportion of actual power to rated power.  Crest factor Proportion of the peak value of load current to the valid value. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 113 Phase voltage (V)/Line voltage (V)/Phase current (A)/Frequency (Hz) Bypass input phase voltage/Bypass input line voltage/Bypass input phase current/Bypass input frequency.  Power factor Proportion of the Bypass input active power to the mains input apparent power. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 114 Battery operating temperature (A battery sensor is required. If this sensor is not installed, NA is displayed.)  Backup time (min) Battery backup time estimated at the current load.  Remaining cap. (%) Remaining battery capacity. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 115 Figure 4-14 Environment data  Ambient temperature (° C) Temperature measured by the ambient temperature and humidity sensor (Install the sensor. If this sensor is not installed, NA is displayed.)  Ambient humid. (%) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 116 Mod. Cur. Eql. Data is displayed only when Cross current monitoring is set to Enable and the number of inverter power modules is greater than 1. Figure 4-15 Mod. Cur. Eql. data PDU Data Figure 4-16 PDU data Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 117 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-17 PDU-IT1 Figure 4-18 PDU-A/C Figure 4-19 Electricity statistics Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 118 January 2016, set the start date to 2016-01 and end date to 2016-02. If you set both the start date and end date to 2016-01, a message will be displayed, indicating wrong query dates. Figure 4-20 ATS 1 Figure 4-21 ATS 2 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 119: Alarms Screen

    On the System Info screen, tap to enter the Alarms screen. On the Alarms screen, you can view active alarms and historical alarms, clear faults, and control the buzzer. Figure 4-23 Alarms screen Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 120 If the buzzer is enabled, Buzzer Off is displayed on the operation screen. If you enable the buzzer, the buzzer buzzes when a critical alarm, a minor alarm, or a certain warning is generated. If you mute the buzzer, it never buzzes. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 121: Settings Screen

    The icon of the corresponding integrated UPS in the device layout diagram on the APP will blink for 10s. 4.1.2.4 Settings Screen On the System Info screen, tap . The Settings screen is displayed. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 122 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-28 Settings screen 1 Figure 4-29 Settings screen 2 Figure 4-30 Settings screen 3 Basic Settings Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 123 If the password complexity check is enabled, the password is required to be a string of 6-20 characters and contain at least two types of characters. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 124 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Communication Figure 4-33 Communication screen 1 Figure 4-34 Communication screen 2 Figure 4-35 Communication screen 3  IP address allocation Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 125 Set an Ethernet subnet mask that ranges from 0.0.0.0 to 255.255.255.255. The default value is 255.255.255.0.  Gateway Set an Ethernet gateway that ranges from 1.0.0.0 to 223.255.255.255. The default value is 192.168.0.1. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 126 When using the mobile app for site setup or inspection, set WiFi SSID after connecting a WiFi module over a USB port to identify the WiFi device to which the mobile phone is connected.  Password The password for accessing WiFi. Basic Parameter Settings Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 127 2 V or 12 V. The number of cells must be a multiple of 12 (for example, 180 and 192).  Cell float voltage, Cell equalized volt, Float volt. temp. comp. coef., and EOD voltage threshold are set for cells. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 128 Set System capacity and Power module capacity according to specifications. Incorrect settings may cause an overload alarm, which affects normal UPS running. Figure 4-37 Advanced Param. screen 1 Figure 4-38 Advanced Param. screen 2 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 129 A dual-bus system consists of one master and one slave BSC system, which are − specified by the customer. A BSC system cannot be the master and slave at the same time. Specify master and slave systems during deployment. To change the setting, Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 130 Capacitor failure detection upper limit and Capacitor failure detection lower limit. If the power module determines that the inverter capacitor is faulty, it shuts down the inverter to prevent the fault from expanding.  Capacitor failure detection upper limit (A) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 131  Altitude (m) Set this parameter based on the altitude of the place where the rack is used. The default value is less than or equal to 1000. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 132 In this mode, the total distortion of the input current waveform (THDi) is poor, but the system is stable. Weak input adaptability is suitable for mains and AC input sources. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 133 This parameter specifies the number of transfers between bypass mode and normal mode within 1 hour, which ensures system security. The value can be 1 to 10, 5 by default. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 134 The values can be ± 5% (default), ± 6%, ± 7%, ± 8%, ± 9%, or ± 10%.  BPM mode upon BPM overtemp. This parameter specifies whether to start bypass mode if overtemperature occurs. Battery Parameter Settings Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 135 BMU. If the BMU is not configured, you do not need to set these two parameters. Figure 4-44 Battery Param. screen 1 Figure 4-45 Battery Param. screen 2 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 136 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-46 Battery Param. screen 3 Figure 4-47 Battery Param. screen 4 Figure 4-48 Battery Param. screen 5 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 137 When batteries are continuously under float charging or hibernation, you can enable forced equalized charging. When the forced equalized charging time reaches the value of this parameter, float charging starts.  Equalized charging protection interval (d) and Scheduled equalized charging interval (d) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 138 The backup time alarm threshold is 3–30 min, and the default value is 5 min. The remaining capacity alarm threshold is 5%–50%, and the default value is 20%. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 139 Monitoring interface card (MUS05A): provides four routes of configurable output dry contact signals.  Dry contact extended card (MUE07A): provides two routes of input signals and one route of output signals. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 140 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-50 Dry Contacts screen 1 Figure 4-51 Dry Contacts screen 2 Figure 4-52 Dry Contacts screen 3 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 141 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-53 Dry Contacts screen 4 Figure 4-54 Dry Contacts screen 5 Figure 4-55 Dry Contacts screen 6 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 142 PDU input surge protector or system output switch.  MUE06A connection If this parameter is enabled, the mains and bypass backfeed protection is enabled. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 143 Corresponds to signal of the input dry contact DI_1 on the MUE07A.  MUE07A DI_2 Corresponds to signal of the input dry contact DI_2 on the MUE07A.  MUE07A DI_3 Corresponds to signal of the input dry contact DI_3 on the MUE07A. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 144 D.G. power supply when an outage occurs. For details about the installation and configurations, contact Huawei technical support.  Works with the intelligent power supply device.  D.G startup batt. volt. (V/cell) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 145 Works with the intelligent power supply device. The value range is 1.80-2.00 V/cell, and the default value is 1.80 V/cell. PDU Parameters Settings Figure 4-59 PDU Parameters screen 1 Figure 4-60 PDU Parameters screen 2 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 146 1.5 Hz. When the system frequency is higher than the rated frequency plus the value of this parameter or is lower than the rated frequency minus the value of this parameter, an alarm is generated.  Branch breaker open alarm enable Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 147 Main route current three-phase load imbalance alarm threshold. The value range is 5.0%–50.0%, and the default value is 25.0%. When the value obtained after the difference between the maximum and minimum main route three-phase currents is Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 148: Maintenance Screen

    Disable, the system does not generate a branch route current alarm under any condition. The default value is Disable. 4.1.2.5 Maintenance Screen On the System Info screen, tap . After you log in, the Maintenance screen is displayed. Figure 4-63 Maintenance screen 1 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 149 Test, and Capacity Test. The next maintenance time displayed on the screen reminds you of the upcoming time to check batteries. Figure 4-65 Battery Maint. screen Button is available only when it is in green. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 150 Figure 4-67 USB Operations screen 2 Inv. ON and Inv. OFF You can start and shut down the inverter using the LCD. Before the inverter starts, the system asks for confirmation to prevent misoperation. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 151 ECM and it is working, perform active/standby switchover on the ECM. After switchover, ensure that the ECM stops working (the yellow or red indicator is on, or the green indicator is blinking) before you maintain it. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 152 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-70 ECM Switchover screen Screen Calib. You can calibrate the screen. Figure 4-71 Screen Calib. screen Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 153: About Screen

    On the System Info screen, tap About on the About screen, you can view the UPS model, manufacturer name, monitoring version and power version. To view version details, tap Version Info. Figure 4-73 About screen Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 154: System Status Screen

    On the main screen, tap Common Functions. On the Common Functions to query the AC output, load, and mains input information, start or shut down the inverter, control the buzzer, and query the historical alarms. Figure 4-75 Common Functions screen 1 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 155: Webui

    Step 1 Open the browser and choose Tools > Internet Options. Step 2 On the Advanced tab page, ensure that Use TLS 1.0, Use TLS 1.1, and Use TLS 1.2 are selected and click OK. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 156 Performs all operations on the LCD and administrator) WebUI, including system running information Changeme browsing, system information (historical alarms, logs, e-labels, and fault data) exporting, parameter (system parameters and battery parameters) setting, system control Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 157 After a user logs in to the WebUI, if another user logs in with the same user name, the current account will be logged out.  It is advised to change the password after the first login using User Mgmt. on the Config. page to prevent unauthorized access. ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 158: Monitoring Page

    You can click the UPS, PDU-IT, and PDU-A/C icons in the energy flow diagram to view detailed information about them. You can click to go back to the energy flow diagram page. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 159: Active Alarms Page

    UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-79 UPS Figure 4-80 PDU-IT1 Figure 4-81 PDU-A/C 4.2.2.1 Active Alarms Page The Active Alarms page details active alarms. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 160: Real-Time Data Page

    Param. Settings page, you can set basic parameters, advanced parameters, input parameters, output parameters, bypass parameters, battery parameters, and dry contacts. The settings are the same as those on the LCD. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 161: Comm. Config. Page

    Open the Comm. Config. page to set communications information. The settings are the same as those on the LCD. Figure 4-85 Comm. Config. page 4.2.2.5 Control Page Open the Control page to control the system running. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 162: Query Page

    On the Logs page, you can set Log to Historical logs, Cap. test logs, or Common test logs, and query or export logs. Historical logs can be exported but not queried. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 163: Config. Page

    6–20 characters and contain at least two types of characters. 4.2.4.2 Site Config. page On the home page, choose Config. > Site Config.. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 164 Configure Alarm Notification Email Address is used to configure the email address for receiving alarm emails from the monitoring system.  ModbusTCP Certificate Management: ModbusTCP supports the Transport Layer Security (TLS) secure protocol for encrypted transmission and implements access Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 165: Maint. Page

    On the homepage, click the Maint. tab. The Maint. page provides the Calib., Commissioning Var., Upgrade, Download, Bus Capa. Life, and Cur. Equal. Data tabs. Figure 4-91 Calib. Figure 4-92 Commissioning Var. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 166 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 4 User Interface Figure 4-93 Upgrade Figure 4-94 Download Figure 4-95 Bus Capa. Life Figure 4-96 Cur. Equal. Data Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 167: Operations

    Context Perform system commissioning and power-on strictly according to the system manual and ATS instructions. For any changes in operations and parameters, consult Huawei engineers. Otherwise, system commissioning or power-on may fail, or even the cabinet is damaged. Issue 09 (2019-12-20)
  • Page 168 Number of Phases Single phase; three-phase The default value is four-wire; three-phase three-wire three-phase four-wire. Secondary load Not Used; Opening Only; The default value is Not Opening And Closing Used. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 169  Local / Remote Language English; Deutsch; Set the parameter Francais; Itatiano; based on site Espanol; Suomi; requirements. Russian; Chinese Step 8 Set the ATS controller to auto mode. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 170: Powering On And Starting The Ups

    Step 1 (Skip this step in the case of ATS input.) Turn on the MCCB. Step 2 Turn on the UPS input circuit breaker QF1. The UPS is powered by the mains and initialization begins. The LCD displays the Huawei logo and an initialization progress bar.
  • Page 171 150 Ah and two battery strings are connected in parallel to the UPS, set the battery capacity to 300 Ah.) Number of cells Indicates the number of 2 V batteries in a battery string connected to the UPS. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 172 If dry contact signals are connected to the system, choose System Info. > Settings > Dry contacts and check that the connected dry contacts have been enabled and that the disconnected dry contacts have been disabled. Step 3 (02311FTE-004, 02311FTE-006, 02311FTC-006 and 02311FTC-004 cabinets) Set ATS parameters. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 173 User Manual (Integrated UPS 3.0) 5 Operations Figure 5-2 ATS parameters screen 1 Figure 5-3 ATS parameters screen 2 Figure 5-4 ATS parameters screen 3 Table 5-6 ATS parameter settings Item Value Description Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 174 DG stop delay (s) 1–1800 The default value is 10. Step 4 View the system running status diagram on the LCD to check that the UPS is working in bypass mode. ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 175 User Manual (Integrated UPS 3.0) 5 Operations The Service Expert app can be downloaded from Huawei app store and can run on Android. User interfaces displayed in this document correspond to the app version V100R001C00B055 and are for reference only.
  • Page 176 Step 6 Tap Login after setting the parameters. Step 7 After login, tap Power-on password activation on the screen. A message is displayed, indicating whether to start the UPS. Tap OK. Figure 5-6 Power-on password activation ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 177 Step 4 On the LCD, choose System Info > Maintenance > Inv. ON. You can obtain the Bar code and Verification code from the screen, as shown in the following figure. Figure 5-8 Offline startup Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 178: Non-Initial Startup

    You can also start the inverter by choosing System Info > Maintenance > Inv. ON. Step 2 In the displayed login screen, select a user name and enter the password. Step 3 In the displayed dialog box, tap Yes to start the inverter. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 179 Figure 5-10 Setting the Internet options Step 3 In the address box of the browser, enter https://UPS IP address. Step 4 Enter the correct user name and password and click Login. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 180: Powering On Loads

    After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears. Check that the UPS has transferred to normal mode by viewing the system running status diagram. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 181 UPS. After you turn on the battery string input switch, the No battery alarm disappears. Step 4 Turn on the UPS output circuit breaker QF3. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 182: Optional) Setting Bsc Mode

    Info > Settings. Tap Advanced Param. on the Settings screen. On the displayed screen, set BSC mode to BSC master mode. If you have not logged in, enter a user name and password, and tap on the displayed login screen. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 183: Shutting Down And Powering Off The Ups

    After you shut down the inverter, if the bypass is normal, the UPS transfers to bypass mode; if the bypass is abnormal, the UPS supplies no power. Before you shut down the UPS, ensure that all loads have shut down. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 184 Select a language. Enter a user name and password, and click Login to open the homepage. On the homepage, choose Monitoring > Control, and click Inv. OFF. In the displayed dialog box, click OK to shut down the inverter. Figure 5-18 Shutting down the inverter Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 185 Step 4 Turn off UPS input circuit breaker QF1. Step 5 Turn off the UPS input circuit breaker (for MCCB input) or disconnect the mains from the ATS (for ATS input). ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 186: Starting The Ups In Battery Mode

    Step 4 Press and hold down the BATT start button on the bypass module for at least 2 seconds. The system automatically enters the battery cold start status. The LCD displays the Huawei logo and an initialization progress bar.
  • Page 187: Setting Eco Mode

    Step 2 Select a value (± 5%, ± 6%, ± 7%, ± 8%, ± 9%, or ± 10%) from the ECO voltage range drop-down list box. Figure 5-22 Setting ECO voltage range Step 3 Set Working mode to ECO. Information indicating that the UPS works in ECO mode is displayed on the LCD. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 188 After the inverter starts, the UPS still works in bypass mode and the inverter is standby. If the bypass is abnormal, the inverter supplies power immediately. If the inverter is not started, the UPS may be disconnected. Figure 5-24 System Status screen ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 189: Testing Batteries

    The forced equalized charging test duration reaches the forced equalized charging protection time (12–24 h, 18 h by default).  The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.  An alarm is generated. ----End 5.9.2 Shallow Discharge Test Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 190 The battery discharge capacity reaches the specified value (10%–50%, 20% by default).  The discharge voltage reaches the warning threshold (calculated in real time).  The load ratio fluctuation exceeds 10%.  An alarm is generated. ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 191: Capacity Test

    Save the capacity test data record with the largest discharge capacity in a month as the capacity test data for the month. A maximum of recent 36 capacity test records can be saved. ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 192: Test Data Download

    Step 3 Choose USB Operations > Export Logs, and select a log download path. Figure 5-28 Downloading logs Step 4 Tap Next. In the displayed dialog box, tap Yes to download data. Figure 5-29 Confirming the path ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 193: Download Over The Webui

    Step 2 Remove the screws using a Phillips screwdriver, remove the barrier chip on the maintenance bypass switch, and turn on the maintenance bypass switch. The Maint. breaker closed alarm is displayed in the alarm list. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 194: Transferring From Maintenance Bypass Mode To Normal Mode

    The Maint. Breaker closed alarm disappears from the alarm list. Check whether the UPS works in bypass mode by viewing the system running diagram on the LCD or WebUI. Step 2 Start the inverters. ----End 5.12 Performing EPO Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 195: Clearing The Epo State

     Choose System Info from the main screen, tap . On the displayed Alarms screen, tap Clear Faults. In the displayed dialog box, tap Yes, The EPO alarm is cleared successfully. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 196 Figure 5-33 Alarms screen Figure 5-34 Clearing the alarm  WebUI On the homepage, choose Monitoring > Control, and click Clear Fault to clear the EPO alarm. Figure 5-35 Clearing the alarm Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 197: Exporting Data

    Procedure Step 1 Choose Query > Historical Alarms, and set Severity, Generated, and Cleared. Figure 5-36 Querying historical alarms Step 2 Click Query, and you can see the corresponding historical alarms. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 198: Setting Hibernation Mode

    . The Settings screen is displayed. If you have not logged in, enter a user name and password, and tap on the login screen displayed. Step 2 Tap Advanced Param.. Tap to browse the parameter. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 199 Figure 5-38 Hibernation parameters on the LCD Step 3 On the LCD, set Paral. sys. hibernate to Enable. A confirmation message and security warning are displayed. Figure 5-39 Confirmation message Figure 5-40 Security warning Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 200: Webui

    Before you connect the D.G. to a UPS system, check that the system is a single UPS system and that the system is working in non-inverter mode and has connected to batteries. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 201: Settings On The Lcd

    Intelligent power can be set to Enable and Disable. The intelligent power supply function can be used only when Intelligent power is set to Enable. It is set to Disable by default. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 202 Step 4 When Intelligent power is set to Enable, the system will automatically modify some parameter settings which you can view on the corresponding screen. Figure 5-44 Parameters associated with intelligent power supply 1 Figure 5-45 Parameters associated with intelligent power supply 2 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 203 User Manual (Integrated UPS 3.0) 5 Operations Figure 5-46 Parameters associated with intelligent power supply 3 Figure 5-47 Parameters associated with intelligent power supply 4 Figure 5-48 Parameters associated with intelligent power supply 5 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 204 In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and the D.G. runs for 15 minutes), the signal for shutting down the D.G. is triggered. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 205: Settings On The Webui

    V/cell. It is available only when Intelligent power is set to Enable. When the D.G. is connected, ensure that the preceding three parameters have been set so that the UPS can run properly. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 206 Figure 5-51 Parameters associated with intelligent power supply 1 Figure 5-52 Parameters associated with intelligent power supply 2 Figure 5-53 Parameters associated with intelligent power supply 3 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 207 User Manual (Integrated UPS 3.0) 5 Operations Figure 5-54 Parameters associated with intelligent power supply 4 Figure 5-55 Parameters associated with intelligent power supply 5 Figure 5-56 Parameters associated with intelligent power supply 6 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 208: Ats Scenario

    The D.G. and mains connect to the UPS over an ATS. The MDU obtains the D.G. startup/shutdown status over the dry contact signals sent from the ATS, and controls D.G. startup/shutdown over dry contacts. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 209 The D.G. RUN port of the ATS connects to the dry contact card. Figure 5-58 Connecting signal cables in the ATS scenario (1) The AMF port of the ATS connects to the DI_5 port on the dry contact extended card. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 210 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 5 Operations Figure 5-59 Connecting signal cables in the ATS scenario (2) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 211: Routine Maintenance

    Power grid Input voltage: 380 V AC, 400 If the input voltage is environment V AC, or 415 V AC (line abnormal, check the power grid voltage) status and input cable Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 212: Quarterly Maintenance

    The insulation layer of  Replace the cables. (between the UPS and the cables is intact and terminals  Secure the output power distribution cabinet) are free from black marks terminals. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 213: Battery Maintenance

    Before installing batteries, read through the battery user manuals and pay attention to safety precautions and connection methods provided by battery manufacture. When installing and maintaining batteries, pay attention to the following points: Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 214: Precautions For Battery Maintenance

    Equalized charging voltage: battery string output terminals of battery string (2.35 V/cell ± 1%) x number of and the battery input terminals battery cells at the UPS side is greater than Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 215: Quarterly Maintenance

    2.25 V/cell ± 0.02 V/cell battery exceeds the specifications requirement, perform a complete forcible equalized charging for the battery, and check again whether the voltage is normal. 3. If the fault persists, contact Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 216: Annual Maintenance

    O&M Personnel Skill Requirements O&M personnel must be qualified power distribution system engineers who are familiar with the data center power supply and distribution system configurations and the operations for each core component. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 217: Monthly Maintenance

    If the insulation does not meet resistance of the the insulation resistance is greater the requirement, check and secondary loop than or equal to 2 megohms. maintain each component and signal cables. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 218: Troubleshooting

    EOD voltage and 11.3 V/cell. 2. Restore the mains power supply to start the inverter. Close the battery switch and charge batteries until each battery has a voltage greater than the EOD voltage and 11.3 V/cell. If any unmentioned faults occur, see the alarm list chapter, or contact Huawei technical support. Table 7-1 Troubleshooting...
  • Page 219 Power off the ATS and not normal. powered on, the sequence is incorrect. check the phase sequence. ATS automatically switches from ON to OFF or switches between ON and OFF repeatedly. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 220 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) 7 Troubleshooting For details about component replacement and maintenance involved in Troubleshooting and Alarm List, consult Huawei maintenance engineers. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 221: Parts Replacement

    Fuse of L1 indicator for route I Fuse of L2 indicator for route I FU3/4/5 Main route input L1/L2/L3 fuses (AC INPUT VOLT SAMPLE) FU6/7/8 UPS output U/V/W fuses (IT INPUT VOLT SAMPLE) Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 222 Fuse of L3 indicator for route I FU10 Reserved Figure 8-1 Fuse (1) Cover (2) Fuse Procedure Step 1 Remove the protective panel. Step 2 Locate the fuse terminal in the UPS according to the diagram. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 223: Replacing An Indicator

    Spare indicators of the same model are available and functional. Tools and Materials  Phillips screwdriver  Key to the UPS  Protective gloves  Multimeter  Step ladder  Spare indicator Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 224 Step 2 Remove the protective panel. A cabinet with ATS input is used as an example. Figure 8-3 Removing the protective panel Step 3 Remove the indicator fastener using a Phillips screwdriver. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 225 Step 7 Put a new indicator in the mounting hole, secure the retaining ring, and connect the conducting wire. Step 8 Install the new indicator in the fastener and reinstall the fastener in the cabinet. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 226: Replacing A Circuit Breaker

    Figure 8-6 Removing the circuit breaker Remove and install the circuit breaker using an extracting kit. Do not operate barehanded. Step 3 Remove the copper bar and install it on the new circuit breaker. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 227: Replacing An Ats

    ATS input terminal is not energized. Step 2 Switch off the output and input circuit breakers in the UPS cabinet. Step 3 Remove the protective cover. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 228 Step 4 Remove the copper bar from the ATS. Figure 8-10 Removing the copper bar Step 5 Remove the bolts that secure the inner side of the cabinet to the copper bar. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 229 Figure 8-11 Removing the bolts that secure the inner side to the copper bar Step 6 Remove the indicators. Figure 8-12 Removing the indicators Step 7 Remove the signal cable terminals from the ATS. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 230 Step 9 Secure the new ATS. It is recommended that you install the two bolts on the top before securing the ATS. Step 10 Reinstall the ATS signal terminals and indicators. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 231 Step 13 Switch on the upstream power distribution circuit breaker of the UPS cabinet, and use a multimeter to check that the ATS input voltage is normal. Step 14 Switch on the input and output circuit breakers of the UPS cabinet. ----End Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 232: Technical Specification

    4000 m, the rated power should be derated. For details, see the IEC62040-3.) Table 9-3 Safety and EMC Item Specifications Safety compliance EN62040-1, 2013 IEC62040-1, 2013 Electromagnetic EN/IEC62040-2 compatibility (EMC) IEC61000-2-2 IEC61000-4-2 Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 233 360–528 V DC (30–44 batteries, 32 by default; derated by 6% when there are 30 batteries) Battery management Intelligent battery management Cold start When a mains outage occurs, batteries can start the UPS to Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 234 Derating coefficient of  40 A circuit breaker: 0.75 output circuit breakers  63 A circuit breaker: 0.7 Table 9-8 System electrical specifications Item Specifications System efficiency 96% (linear load) Current equalization specification Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 235: A Menu Hierarchy

    Battery Status Module Data Total Runtime Environment Data PDU Data Cabinet Input Mod. Cur. Eql. Data Alarms Active Alarms Historical Alarms Buzzer Off Clear Faults Twinkle Settings Basic Communication Basic Param. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 236 Export Config. Export Logs Export E-labels Export Alarms Multi-brand Fault Data Upgrade Software Inv. ON Inv. OFF ECM Switchover Screen Calib. Bus Capa. Life Set PDU address About Model Manufacturer Monitoring Version Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 237: Menus On The Webui

    Frequency Power factor Inv. ON Inv. OFF Buzzer Off Historical Alarms System Status ATS/MCCB PDU-IT1 PDU-IT2 PDU-A/C A.2 Menus on the WebUI Level 1 Menu Level 2 Menu Level 3 Menu Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 238 Ambient Temperature and Humidity Sensor Settings BMU Settings CIM Control NTC Settings WiFi Settings Control System Commands and Tests Query Alarm History Query Export Logs Historical log Cap. test log Common test log Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 239 ModbusTCP Certificate Management ModbusTCP CA Certificate Management ModbusTCP Authentication eUPS Certificate Management Maint. Calib Bypass Module Commissioning Var. Bypass Module Upgrade Upgrade UPS Software Download Download Bus Capa. Life Bus Capa. Life Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 240 UPS5000-E-(50 kVA-125 kVA) User Manual (Integrated UPS 3.0) A Menu Hierarchy Level 1 Menu Level 2 Menu Level 3 Menu Cur. Equal. Data Mod. Cur. Eql. Data Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 241 QF1 indicates the first switch in the single-input scenario. Table B-1 Symbols Symbol Name Symbol Name Circuit breaker SPD circuit breaker Surge protective device Fuse (SPD) Automatic transfer switch MCCB Molded case circuit breaker Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 242 Replace the faulty module. 0001-3 The mains is not Check the mains. normal. 0004-1 Mains ph. Reversed Minor Cable connections Verify the cable connections. are incorrect. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 243 If no, correct the installation. 2. Check whether the battery input voltage of the UPS is normal. If yes, the battery sampling circuit of the power Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 244  The battery 2. Check whether the battery ground grounding failure detector is Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 245 2. Check whether the fans are functioning properly. Replace  The air channel the power module if the fans for the power are faulty. module is Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 246 10 seconds later. 1. Check that there is no 0564-1 Overload timeout Critical  The load is overload. excessive. 2. Check that the module power Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 247 3. Replace the ECM.  Only one rack works in a parallel system.  An ECM is faulty. 0583-4 The inter-rack Replace the inter-rack parallel industrial frequency Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 248  Check that the configured rack appropriate. capacity meets requirements. 0090-1 Dry contact board Critical I2C communication Replace the dry contact board fault with the dry contact MUE05A. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 249 No further measures are required. OFF. 0340-1 Maint. breaker Minor The UPS The running status is displayed. closed No further measures are required. maintenance circuit breaker is ON. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 250 3. Rectify any bypass SCR incorrect. open-circuit.  The bypass SCR open-circuits. 1. Check that the bypass output 0150-1 Inverter Minor  The bypass frequency does not change asynchronous frequency Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 251 MDU and set the working manual. mode to automatic. 0380 In self-check Warning The inverter is in Wait until the inverter self-check self-check. is complete. Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 252 BCB-BOX battery bus bar box BBB-BOX Conformite Europeenne digital signal processing economic control operation emergency power off energy control module end of discharge International Electrotechnical Commission liquid crystal display Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.
  • Page 253 SNMP Simple Network Management Protocol total distortion of the input THDi current waveform total harmonic distortion THDv of output voltage uninterruptible power system Universal Serial Bus VRLA valve-regulated lead acid battery Issue 09 (2019-12-20) Copyright © Huawei Technologies Co., Ltd.