Huawei OptiX OSN 2500 Quick Installation Manual page 62

Hide thumbs Also See for OptiX OSN 2500:
Table of Contents

Advertisement

Installation procedure
1
L1
A
Strip a part of the insulation layer B of the power
cable according to the cross-sectional area of the
conductor, and ensure that the conductor C of the
power cable is exposed for the length L1.
When stripping the insulation layer of a power cable, do not damage the metallic conductor of the power cable.
After the conductor is routed into the cord end terminal, the exposed part of the conductor of the power cable
cannot be more than 1 mm long.
H
W2
W1
3
Determine the cross-sectional area and crimp the
joint parts of the cord end terminal and the conductor
of the power cable using a crimping tool.
B
C
A
4
59
2
A
Route the conductor of the power cable into the cord
end terminal A, and then align the conductor with the
edge of the cord end terminal.
4
2
Cross-Sectional Area (mm
)
0.25
0.5
1.0
1.5
2.5
4
6
10
16
After crimping the terminal, check the maximum width of
the terminal, which needs to be less than the maximum
width specified in the table.
B
Maximum Width (mm)
1
1
1.5
1.5
2.4
3.1
4
5.3
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents