6. (Optional) After the quick settings are complete, if the monitoring page displays alarms, clear the
alarms.
For system security purposes, change the preset password upon first login.
7. Turn on the input switches on the front panel of the PDC.
8. Switch on the output circuit breakers except reserved circuit breakers in the PDC in sequence to
power on the corresponding devices and check whether the monitoring parameters on the MDU
screen are correct.
9. (Optional) Power off the PDC.
a) Turn off the output switches in the PDC.
b) Turn off the input switches in the PDC.
c) Turn off the input power circuit breaker.
a) If this is the initial startup, set the
language, time, date, network parameters,
and system parameters by using the
Settings Wizard.
b) If this is not the initial startup and these
parameters have been set before, the
system uses the existing settings by default.
NOTE
The figures are for reference only. The
actual parameter values prevail.
16