Alarm Name
Possible Cause
Overdischarge
The battery voltage
Protection
is too low.
The device is
faulty.
Discharge
The battery is faulty.
Overcurrent
Protection
Charge
The battery is faulty.
Overcurrent
Protection
Battery
An electrochemical
Electrochemica
cell is faulty.
l Cell n Fault
Board
The device is faulty.
Copyright © Huawei Technologies Co., Ltd.
5 Alarms and Troubleshooting
Solution
check whether the alarm is
cleared.
If yes, no further action is
required.
If no, contact Huawei
technical support.
1. Check whether the AC
voltage is abnormal.
If yes, rectify the power
grid fault.
If no, contact Huawei
technical support.
1. Switch off the battery circuit
breaker and check whether
the battery voltage is
abnormal.
If yes, replace the battery.
If no, go to the next step.
2. Check whether the function
module has a communication
failure alarm.
If yes, handle the alarm.
If no, contact Huawei
technical support.
1. Switch off the battery circuit
breaker and check whether
the battery voltage is
abnormal.
If yes, replace the battery.
If no, go to the next step.
2. Check whether the function
module has a communication
failure alarm.
If yes, handle the alarm.
If no, contact Huawei
technical support.
1. Replace the battery and
check whether the alarm is
cleared.
If yes, no further action is
required.
If no, contact Huawei
technical support.
1. Replace the device and check
45