Huawei PowerCube 500 User Manual page 48

Hide thumbs Also See for PowerCube 500:
Table of Contents

Advertisement

PowerCube 500 (CPS300-N18A1H)
User Manual
Indicator
Status
Steady red
Issue 02 (2019-08-30)
Alarm Name
Possible Cause
overvoltage occurs.
Ambient
overtemperature
occurs.
53VDC output
Output overpower
Protect
occurs.
Output overcurrent
occurs.
53 V DC output
overvoltage occurs.
Ambient
overtemperature
occurs.
High
Ambient
Temperature
overtemperature
Protect
occurs.
24VAC
The 24 V module
Module Fault
hardware in the
module is faulty.
53VDC
The 53 V module
Module Fault
hardware in the
module is faulty.
Solar Function
The solar function unit
Unit Module
is abnormal.
Fault
AC Module
The AC module
Fault
hardware in the
module is faulty.
AC Surge
The module SPD
Protector Fault
provides
insufficient surge
protection.
The module is
abnormally
Copyright © Huawei Technologies Co., Ltd.
5 Alarms and Troubleshooting
Solution
If no, go to the next step.
2. Check whether the function
module surface temperature
at noon is less than 45° C.
If yes, contact Huawei
technical support.
If no, add a sunshade.
1. Check whether the 53 V DC
output port is short-circuited
or overloaded.
If yes, rectify the short
circuit or reduce the load.
If no, go to the next step.
2. Check whether the function
module surface temperature
at noon is less than 45° C.
If yes, contact Huawei
technical support.
If no, add a sunshade.
1. Check whether the operating
ambient temperature of the
function module is greater
than 45° C.
If yes, add a sunshade.
If no, contact Huawei
technical support.
Replace the function module.
Replace the function module.
Replace the function module.
Replace the function module.
1. Replace the function module.
2. Check whether the AC input
cables are routed overhead to
the function module or
whether the function module
is used for an expressway
42