Alarms And Troubleshooting; Function Module - Huawei PowerCube 500 User Manual

Hide thumbs Also See for PowerCube 500:
Table of Contents

Advertisement

PowerCube 500 (CPS300-N18A1H)
User Manual

5.1 Function Module

Table 5-1 Alarms and troubleshooting (power unit)
Indicator
Status
Blinking
yellow
Issue 02 (2019-08-30)
5

Alarms and Troubleshooting

Alarm Name
Possible Cause
AC
Overvoltage
AC
Undervoltage
LLVD Low
The battery voltage
Voltage
drops to the load low
Disconnected
voltage disconnection
(LLVD) voltage
threshold due to a
long-time AC power
failure.
Copyright © Huawei Technologies Co., Ltd.
The AC voltage is
too high.
The AC detection
circuit of the
module is faulty.
The AC input
voltage is too low.
Cables are loose.
5 Alarms and Troubleshooting
Solution
1. Check whether the AC input
voltage is abnormal.
If yes, locate the cause
and rectify the fault to
prevent high voltage from
damaging the function
module.
If no, contact Huawei
technical support.
1. Check whether the AC input
voltage is abnormal.
If yes, rectify the power
grid fault.
If no, go to the next step.
2. Check that cables are
connected properly.
If yes, contact Huawei
technical support.
If no, reconnect the
cables.
1. Check whether the battery is
discharging due to a
long-time AC power failure.
If yes, rectify the power
grid fault.
If no, go to the next step.
2. Check whether the LLVD
voltage threshold is
38

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cps300-n18a1h

Table of Contents