CI5x1
Hot Swap
H = Hot swap
88
WARNING!
Risk of explosion or fire in hazardous environments during hot swapping!
Hot swap must not be performed in flammable environments to avoid
life-threatening injury and property damage resulting from fire or explosion.
WARNING!
Electric shock due to wrongdoing during hot swapping!
To avoid electric shock
follow these conditions for hot swapping:
Digital outputs are not under load.
Input/output voltages above safety extra low voltage/
protective extra low voltages (SELV/PELV) are switched off.
Modules are completely plugged on the terminal unit with both snap fit
engaged before switching on loads or input/output voltage.
Never touch exposed contacts (dangerous voltages).
Stay away from electrical contacts to avoid a skipping arc.
Do not operate improperly mechanical installation.
Hot swap
System requirements for hot swapping of I/O modules:
Hot-swappable terminal units have the appendix TU5xx-H.
I/O modules as of index F0.
Communication interface modules CI5xx as of index F0.
The index of the module is in the right corner of the label.