Table 2-8: Dry Contact Operation (Customer ID = 0)

Pin No.
B1
A1
B2
A2
B3
A3
B4
A4
B5
A5
B6
A6

Table 2-9: Dry Contact Operation (Customer ID = 1)

Pin No.
B1
A1
B2
A2
B3
A3
B4
A4
B5
A5
B6
A6

Table 2-10: Dry Contact Operation (Customer ID = 2)

Pin No.
B1
A1
B2
A2
B3
A3
B4
A4
B5
A5
B6
A6
SMPS Assembly with 1 phase AC input has auxiliary connectors for the status of the SMPS.
English 8/2019. Rev 0.0
Pin Name
Major Common
Major Normal Close
Major Normal Open
Minor Common
Minor Normal Close
Minor Normal Open
Charge Common
Charge Normal Close
Charge Normal Open
Reserved
Input
GND
Pin Name
Major Common
Major Normal Close
Major Normal Open
Minor Common
Minor Normal Close
Minor Normal Open
MCCB Status Common
MCCB Status Normal Close
MCCB Status Normal Open
Reserved
Input
GND
Pin Name
Discharge Prohibit Common
Discharge Prohibit
Normal Close
Discharge Prohibit
Normal Open
Charge Prohibit Common
Charge Prohibit
Normal Close
Charge Prohibit
Normal Open
MCCB Status Common
MCCB Status Normal Close
MCCB Status Normal Open
Reserved
Input
GND
Function
Over-Voltage Protection
Under-Voltage Protection
Over-Temperature Protection
Over-Current Protection
Voltage Imbalance Error
Voltage Sensing Error
Under Temperature protection
Temperature Imbalance Error
Charge Stop Set Condition
1. Overvoltage alarm(4.25V/Cell)
2. SOC 100%
Charge Stop Release Condition
1. SOC < 97% or Discharge Current >│3A│
Set Condition: UPS closes B6, A6 contacts for more than 3 second.
Action : Battery MCCB Trip
Function
Over-Voltage Protection
Under-Voltage Protection
Over-Temperature Protection
Over-Current Protection
Voltage Imbalance Error
Voltage Sensing Error
Under Temperature protection
Temperature Imbalance Error
All MCCBs are off : 4A, 4B is closed
One of MCCB is on : 5B, 4B is closed
Set Condition: UPS opens B6, A6 contacts for more than 3 second.
Action : Battery MCCB Trip
Function
Undervoltage Protection
Overtemperature Protection
Discharge Overcurrent Protection
Overvoltage Alarm,
Overvoltage Protection
Overtemperature Protection
Charge Overcurrent Protection
All MCCBs are off : 4A, 4B is closed
One of MCCB is on : 5B, 4B is closed
Set Condition: UPS opens B6, A6 contacts for more than 1 second.
Action : Battery MCCB Trip
.
2
Product Description
15