Installing the Product
Important
Change the values according to your system configuration.
[Count] Rack per 1 System: Number of racks connected to the same System BMS
[Count] Module per 1 Rack: Number of modules for each rack (e.g., 136S1P Rack has 17
modules)
[TCPIP] items (IP Address, Subnet Mask, Gateway, Port)
TCP/IP address and port (17.91.30.246/502 by default), subnet mask (255.255.224.0 by default)
and gateway (17.91.1.2 by default) should be changed according to your network environment.
Set the port number to the factory default values
(Port#01: 502, Port#02: 602, Port#03: 702)
[RTU] items: set to the factory default values.
(Baud rate: 0, Parity: 1, Slave ID: 0x27)
[Operation] Neutral Control Enable
Set to "0" if all racks are connected in parallel (default).
Set to "1" if the two racks are connected in series for a three-wire connection.
[Operation] Customer ID
Set according to the dry contact input and output options. Refer to 2.1.3 SMPS Assembly (Type
A / Type B)
124
Figure 3-152: System BMS Install Setting Window