Technical Data; General Specifications - Siemens SIMOTION P320-3 Manual

With panel fronts
Table of Contents

Advertisement

Technical data

9.1

General specifications

General technical data
Order No.
Dimensions
Weight
Supply voltage (DC)
Brief power failure
according to Namur
Maximum power consumption
Noise emission
Degree of protection
Safety
Protection class
Safety regulations
Electromagnetic compatibility (EMC)
General rules (Page 135)
The generation of the 24 VDC supply voltage by the line-side power supply must be made as functional extra-low
1)
voltage with safe electrical isolation according to IEC 60364-4-41 or as SELV in conformity to IEC/UL/EN/DIN-EN
60950-1 and LPS / NEC Class 2.
Climatic ambient conditions
Temperature
During operation
Storage/transport
Gradient
Relative humidity
During operation
Storage/transport
SIMOTION P320-3 and Panel Fronts
Manual, 02/2012
6AU1320-7AB55-3AF0
262x142x47 (WxHxD in mm)
Approximately 2 kg
24 VDC
(19.2 to 28.8 V)
1
Min. 15 ms (at 20.4 V)
Max. 10 events per hour; min. 1 s recovery time
4 A (at 24 V)
<40dB (A) according to DIN 45635-1
IP 20 according to IEC 60529
Protection class I according to IEC 61140
EN 60950-1; UL 60950; CAN/CSA-C22.2 No. 60950-1; UL 508;
CAN/CSA-C22.2 No. 142 or CAN/CSA-C22.2 No. 14-05
Tested according to IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-14
Horizontal mounting position: In RAL: 0° to +55° C
Vertical mounting position / book mounting: 0° to +45° C
Horizontal mounting position: 0° to +40° C
RAL = Restricted Access Location
(installation of device in operating facilities with restricted access, for
example, a locked control cabinet)
-40° C to +70° C
Operating mode: Max. 10° C/h; Storage: 20° C/h; no condensation
Tested acc. to IEC 60068-2-78, IEC 60068-2-30
5% to 80% at 25° C (no condensation)
5% to 95% at 25° C (no condensation)