Fault Codes - Siemens BT300 Applications Manual

Hvac drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Siemens Industry, Inc. • 96
3.7.3

Fault codes

Fault
Fault
Fault name
code
ID
Over-current
1
(hardware fault)
1
Over-current
2
(software fault)
Over-voltage
10
(hardware fault)
2
Over-voltage
11
(software fault)
Earth fault (hard-
20
ware fault)
3
Earth fault (soft-
21
ware fault)
5
40
Charging switch
7
60
Saturation
Table 57. Fault codes and descriptions.
Possible cause
The drive has detected too high a current
(>4*I
) in the motor cable:
H
sudden heavy load increase
short circuit in motor cables
unsuitable motor
The DC-link voltage has exceeded the
limits defined.
too short a deceleration time
high over-voltage spikes in supply
Start/Stop sequence too fast
Current measurement has detected that
the sum of motor phase current is not
zero.
insulation failure in cables or motor
The charging switch is open, when the
START command has been given.
faulty operation
component failure
Various causes:
defective component
brake resistor short-circuit or over-
load
Siemens Application
Remedy
Check loading.
Check motor.
Check cables and connections.
Make identification run.
Check ramp times.
Make deceleration time longer.
Activate overvoltage controller.
Check input voltage.
Check motor cables and motor.
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
Cannot be reset from keypad.
Switch off power.
DO NOT RE-CONNECT POWER!
Contact factory.
If this fault appears simultaneously
with F1, check motor cables and
motor.
24-hour support +1-800-877-7545 (Dial 2)

Advertisement

Table of Contents
loading