Group 3.10: Automatic Reset - Siemens BT300 Applications Manual

Hvac drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Siemens Industry, Inc. • 52
3.5.12

Group 3.10: Automatic reset

Code
Parameter
P3.10.1
Automatic reset
P3.10.2
Restart function
P3.10.3
Wait time
P3.10.4
Trial time
P3.10.5
Number of trials
Auto-reset:
P3.10.6
Under-voltage
Auto-reset:
P3.10.7
Over-voltage
Auto-reset:
P3.10.8
Over-current
P3.10.9
Auto-reset: AI low
Auto-reset: Unit over-
P3.10.10
temperature
Auto-reset: Motor
P3.10.11
overtemperature
Auto-reset:
P3.10.12
External fault
Auto-reset:
P3.10.13
Underload fault
Table 40: Autoreset Settings.
Min
Max
Unit
0
1
0
1
0,10
10000,0
s
0,00
10000,0
s
1
10
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Siemens Application
Default
ID
0 = Disabled
0
731
1 = Enabled
The start mode for Automatic
reset is selected with this
1
719
parameter:
0 = Flying start
1 = According to par. P3.2.4
Wait time before the first
0,50
717
reset is executed.
When the trial time has
elapsed, and the fault is still
60,00
718
active, the drive will trip to
fault.
NOTE: Total number of trials
4
759
(irrespective of fault type)
Auto-reset permitted?
1
720
0 = No
1 = Yes
Auto-reset permitted?
1
721
0 = No
1 = Yes
Auto-reset permitted?
1
722
0 = No
1 = Yes
Auto-reset permitted?
1
723
0 = No
1 = Yes
Auto-reset permitted?
1
724
0 = No
1 = Yes
Auto-reset permitted?
1
725
0 = No
1 = Yes
Auto-reset permitted?
0
726
0 = No
1 = Yes
Auto-reset permitted?
0
738
0 = No
1 = Yes