Fuel System Inspection And Maintenance - GE 60000 Series Operator's Manual

Hide thumbs Also See for 60000 Series:
Table of Contents

Advertisement

Available languages

Available languages

Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Turn the generator off.
2. Remove control board fuse from control board.
3. Disconnect negative battery cable from negative
battery terminal (indicated by NEGATIVE, NEG, or (‑)).
NOTICE Failure to disconnect negative battery cable will result in
equipment failure.
• DO NOT attempt to jump start the generator.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
4. Charge battery with battery charger at 2 Amps until
battery holds 12 Volts. DO NOT exceed 13.7 volts
when charging.
CAUTION With the system switch set to AUTO, the engine could
crank and start at any time without warning, resulting in
minor or moderate injury.
• To prevent possible injury that could be caused by such sudden
starts, always set the system switch to OFF if performing
maintenance on the system.
• Remove the control board fuse before working on or around the
generator or transfer switch.

Fuel System Inspection and Maintenance

Natural Gas / Propane Fuel System
The fuel system installed on this industrial engine has been
designed to various standards to ensure performance and
reliability. To ensure compliance to these standards, follow the
recommended maintanence schedule contained in this section.
Pressure Regulator Maintenance and Inspection
NOTICE The pressure regulator components have been
specifically designed and calibrated to meet the fuel system
requirements of the engine.
If the regulator fails to operate or develops a leak, it should be
repaired or replaced with the OEM recommended replacement
parts.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (‑)).
6. Ensure hardware on both positive and negative
battery terminals is secure.
7. Reinstall control board fuse in control board.
8 . Turn the generator on and place in AUTO mode.
When inspecting the regulator, check for the following items:
• Check for any fuel leaks at the inlet and outlet fittings.
• Check for any fuel leaks in the regulator body.
• Check to ensure the regulator is securely mounted
and the mounting bolts are tight.
• Check the regulator for external damage.
23