Maintenance; Shutdown Alarm Detection System - GE 60000 Series Operator's Manual

Hide thumbs Also See for 60000 Series:
Table of Contents

Advertisement

Available languages

Available languages

Maintenance

Servicing the System
Before performing any generator maintenance, always
perform the following steps:
1. Set generator circuit breaker to its OFF position.
2. Turn the generator off.
3. Remove control board fuse from control board.

Shutdown Alarm Detection System

The generator may have to run for long periods of time
with no operator present. For that reason, the system is
equipped with sensors that automatically shut down the
generator in the event of potentially damaging conditions,
such as low oil pressure, high temperature, over speed, and
other conditions.
The generator's control board shows possible shutdown
alarms descriptions on the digital display.
The possible shutdown alarms are listed below:
• Overspeed
• Underspeed
• Low Oil Pressure
• High Coolant Temperature
• External Shutdown 1
• External Shutdown 2
• External Shutdown 3
• GCB (Generator Circuit Breaker) Fail
• Generator Overvoltage
• Generator Undervoltage
• Generator Overfrequency
• Generator Underfrequency
• Generator CCW Rotation
• Start Fail
• Stop Fail
• Battery Flat
• Voltage Autodetect
16
4. Utility voltage is present at generator control board.
Disconnect power before servicing control board by
removing the fuses from the transfer switch.
5. After all servicing has been completed, replace fuses
in transfer switch, replace control board fuse in
control board, set circuit breaker ON and turn the
generator on.
Reset Shutdown Alarm Detection System
The operator must reset the shutdown alarm detection
system each time it activates.
Refer to the Control Panel Application Guide supplied with
this generator for more detailed information on resetting the
Shutdown Alarm Detection System.
Overspeed
This shutdown alarm is indicated by Overspeed showing
on the digital display. This condition occurs if the engine
speed in greater than 115% of nominal engine RPM, which is
derived from generator frequency.
To remedy the problem, contact your installer or an
authorized dealer.
Underspeed
This shutdown alarm is indicated by Underspeed showing on
the digital display. This condition occurs if the engine speed
drops under the nominal engine RPM.
To remedy the problem, contact your installer or an
authorized dealer.
Low Oil Pressure
This shutdown alarm is indicated by Low Oil Pressure on
the digital display. The unit is equipped with an oil pressure
switch that uses normally closed contacts held open by
engine oil pressure during operation. Should oil pressure drop
below the 8 psi range, switch contacts close and the engine
will shut down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick or contact
your installer or an authorized dealer.