Connecting The Rs485 Communications Cable (Inverter Cascading) - Huawei SUN2000 Series User Manual

Hide thumbs Also See for SUN2000 Series:
Table of Contents

Advertisement

SUN2000-(3KTL-10KTL)-M0
User Manual
5.6.1 Connecting the RS485 Communications Cable (Inverter
Cascading)
Procedure
Step 1 Connect the signal cable to the signal cable connector.
Issue 04 (2019-10-18)
Figure 5-20 Smart Dongle networking
In the Smart Dongle networking scenario, the SmartLogger1000A cannot be connected.
The Smart Power Sensor is necessary for export limitation. Only the DTSU666-H Smart Power
Sensor (provided by Huawei) can be used.
The Smart Power Sensor and Smart Dongle need to be connected to the same inverter.
SmartLogger1000A Networking Scenario
Figure 5-21 SmartLogger1000A networking
In the SmartLogger1000A networking scenario, the Smart Dongle cannot be connected.
A maximum of 80 devices can connect to a single SmartLogger1000A, such as inverters, Smart
Power sensor, and EMI. You are advised to connect fewer than 30 devices to each RS485 route.
The Smart Power Sensor is necessary for export limitation. Select the Smart Power Sensor according
to the actual project.
To ensure the system response speed, the Smart Power Sensor is recommended to be connected to a
COM port separately from inverter COM port.
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
45