Section 6
Connecting
1.
The recommended connection require four analog channels of the IED: two IED voltage
channels are used for the measured quantities for ROTIPHIZ; two more IED voltage channels
are used for the measured quantities for STTIPHIZ.
IED
VOLTAGE MEASURE (V)
CURRENT MEASURE (V)
VOLTAGE MEASURE (V)
CURRENT MEASURE (V)
ANSI11000209 V1 EN-US
Figure 44: Separate analog inputs for stator STTIPHIZ (64S) and rotor ROTIPHIZ (64R)
2.
It is possible to use a mixed connection that requires only two IED voltage channels for both
ROTIPHIZ and STTIPHIZ. REX060 outputs are connected in series. This connection is not
recommended and can be used only in applications where it is prove the possibility to use it.
the use of this connection leads to reduced performances of both ROTIPHIZ and STTIPHIZ.
IED
VOLTAGE MEASURE (V)
CURRENT MEASURE (V)
ANSI11000210 V1 EN-US
Figure 45: Connection to IED with two analogue voltage inputs
64
protection
1MRK 514 026-UUS F
REX060
X61
8
9
STATOR MODULE SIM
10
11
X81
8
9
ROTOR MODULE RIM
10
11
ANSI11000209_1_en.vsd
REX060
X61
8
9
STATOR MODULE SIM
10
11
X81
8
9
ROTOR MODULE RIM
10
11
ANSI11000210_1_en.vsd
Installation manual