Connecting
4.2 Connecting FC430
7. Connect ground to terminal
below at right using a screwdriver.
Note
The terminal box is detachable
For easier access unplug the terminal box. After connecting the wires, plug the terminal box
back in.
8. Tighten cable gland.
9. Mount power supply protection cover and fasten protection cover screw.
4.2.2.8

Finishing the transmitter connection (field mount)

Connection check-up
1. Check individual wire installation by tugging firmly.
2. Firmly tighten cable glands and insert blanking plugs in unused cable entries.
3. Remove O-ring from lid.
4. Reinstate lid and screw in until mechanical stop. Wind back lid by one turn.
5. Mount O-ring by pulling it over the lid and tighten lid cover until you feel friction from the O-
ring on both sides. Wind lid further by one quarter of a turn to seal on the O-ring.
46
L/+
N/-
Protective Earth (PE)
AC connection
Power: 100 to 240 V AC, 47 to 63 Hz
and power to terminals L/+ and N/- in the manner shown
Compact Operating Instructions, 09/2019, A5E39940293-AB
DC connection
Power: 19.2 to 28.8 V DC
SITRANS FC430