M-NET Converter
Photo
Dimensions
CN2M(M-NET)
LED5
1 2
LED1
CND
(Connect to outdoor controller board)
Unit : mm
LED4
LED3
140
Model change from PAC-SF80MA-E
Descriptions
A-control Mr. SLIM models can be connected to "M-NET"
through optional M-NET converter so that they can be
monitored / controlled effictively and meticulously.
Applicable Models
All PU(H)-P
All PUHZ-RP
All PUHZ-P outdoor Units (A-control)
All PUHZ-HRP
Specifications
Supplied from control board
Power
0.6W (at 5V DC, 12V DC)
Power consumption
Mounted inside the electrical utility box of outdoor
Operating conditions
unit. (Tempreture : -20 to 60
less (no condensation))
Weight
0.3kg
CN5
(Connect to outdoor controller board)
LED2
1 2 3 4 5
SW11(M-NET Address<1s digit>)
SW12(M-NET Address<10s digit>)
PAC-SF81MA-E
, humidity : 90% or
E-209

Advertisement

loading

Summary of Contents for Mitsubishi Electric PAC-SF81MA-E

  • Page 1 M-NET Converter PAC-SF81MA-E Model change from PAC-SF80MA-E Descriptions Photo A-control Mr. SLIM models can be connected to "M-NET" through optional M-NET converter so that they can be monitored / controlled effictively and meticulously. Applicable Models All PU(H)-P All PUHZ-RP All PUHZ-P outdoor Units (A-control) All PUHZ-HRP Specifications...
  • Page 2: Safety Precautions

    M-NET Converter PAC-SF81MA-E INSTALLATION MANUAL FOR A-M CONVERTER This manual is written only for the models  PUHZ-RP1.6/2VHA PUHZ-RP4〜6YHA PUHZ-RP35/50VHA type PUHZ-(H)RP100〜140YHA type PUZ-A18NHA, PUY-A12/18NHA PUHZ-RP100〜140YKA PUHZ-RP2.5〜6VHA(-A) PUHZ-RP8/10YHA(-A), RP200/250YHA(-A) PUHZ-(H)(R)P60〜140VHA type PUHZ-RP200/250YHA (-A) PUZ-A24〜42NHA, PUY-A24〜42NHA PUHZ-RP100〜140VKA PU(H)-P1〜4VGA(A), P25〜100VGAA PU(H)-P71/100VHA, PU(H)-P71〜140YHA PU(H)-P1.6〜6YGA(A), P35〜140YGAA PUH-P8/10YE, P8/10MYA, P200/250MYA PUHZ-P200/250YHA(3), PUHZ-RP200/250YHA2, PUHZ-RP200/250YKA SAFETY PRECAUTIONS ● Before starting installation, read the "Safety Precautions" described below. The following precautions must be observed as it describes the serious matters for safety. ● The safety precautions are described with the degree of danger. ● WARNING When you handle wrong, it can lead to death or serious injury. CAUTION When you handle wrong, it can lead to injury or damage to building and furniture. After installation, make test operation and confirm that it works properly, and explain the safety precautions, operation method,  ●   and maintenance to your customers.    Tell your customers to keep this installation manual together with operation manual with them, and when they give or sell this    machine to other person put this installation manual and operation manual with it. WARNING The installation must be done by dealer or qualified person.
  • Page 3: Parts List

    M-NET Converter PAC-SF81MA-E 1. Parts List Wire Marking : INV type  Always  make sure that the markings and  the applicable model match.  If used incorrectly, parts could be  damaged. Wire Marking : NON-INV Always make sure that the  markings and the applicable model  match. If used incorrectly, parts  could be damaged. E-211...
  • Page 4 M-NET Converter PAC-SF81MA-E 2. Installation procedure 【Applicable model : Group A】 ●To protect the wires connected to M-NET board from the edges of       Affix insulation sheets and ③ to the   sheet-metal component, paste the insulation on the edge surface of panel backside of the flange surface on the   sheet-metal before proceeding with the following work. top of the side panel. ③Insulation sheet      Starting from the bottom, mount  ③Insulation sheet lnsulation Sheet ③ to the  L  bend  section on the back of the noise filter  mounting panel.      Position the chamfered section of Plate   ② so that it faces the fan side (the left  side of the drawing) and mount it using  Screw ⑤.      As shown in the illustration, position  M-NET board ① (insulation sheet, with  (Top view of Electric box) CN2M support) on the four corners of Plate ②  so that the DIP switches (SW11, SW12)  SW12 SW11 ①M-NET board are on the terminal block side and then  Control board mount.      ※Push it firmly until you hear it  click      Use terminal screw ⑦ to secure terminal  block ⑥  Chamfered section ③Insulation sheet      ※Terminal block ⑥ has a round boss ...
  • Page 5 M-NET Converter PAC-SF81MA-E 2. Installation procedure 【Applicable model : Group B】 ●To protect the wires connected to M-NET board from the edges of   sheet-metal component, paste the insulation on the edge surface of panel      Pate insulation sheet  ③ on sheet-metal   sheet-metal before proceeding with the following work. so that it completely envelops the edge  surface of sheet-metal. Paste insulation sheet ③ on sheet-metal so that it  completely envelops the edge surface of sheet-metal.      Install M-NET board ① (with insulation  sheets and supports) on the side of  (When viewed from the side of Electric box) Electric box so that the rotary switch  faces up (at the four points indicated by  arrows). ①M-NET board      ※Push it firmly until you hear it  click .        Use terminal screw ⑦ to secure terminal  block⑥       ※Terminal block⑥ has a round boss for  positioning:Fit the round boss into the  positioning hole in steel-plate.      Paste label ⑧ under terminal block ⑥      Use lead wire-A ⑨ to connect CN5 of  M-NET board ① connection and  CNMNT of outdoor control board.      ※Caution Wire Marking:INV type, Connector  Control board color:Red Always make sure that the  markings and the applicable model  match. If used incorrectly, parts could  be damaged. Use lead wire-C ⑪ to connect CND of  M-NET board ① connection and ...
  • Page 6 M-NET Converter PAC-SF81MA-E 2. Installation procedure  【Applicable model : Group C】      Install the M-NET board ① so that the      (SW11, SW12) come front. ①M-NET board Address switches      ※Put it securely until it sounds click.        Install the Terminal block (M-NET) ⑥ on  the Terminal base ④.      ※The  Terminal  base  ④  has  round  boss           for positioning.         Match the round boss to the holes of         the Terminal base ④.      Put the Label ⑧ on the Terminal base ④      ※Not to close the Hole for M-NET  Control board ground.      Install the Terminal base ④ on the  bottom inside of the electric box. Terminal block ⑤Screw    (M4×8) A B S Mounting hole Position hole ⑦Screw (M3×20) ⑥Terminal block (M-NET) Hole for M-NET ...
  • Page 7 M-NET Converter PAC-SF81MA-E 2. Installation procedure  【Applicable model : Group D】 ①M-NET board      Install the M-NET board ① so that the      (SW11, SW12) come front.      ※Put it securely until it sounds click.   SW12 SW11 Address switches      Install the Terminal block (M-NET) ⑥ on  the base of the electric box.      Put the Label ⑧ on the base of the  electric box. Control board Mounting hole ⑦Screw (M3×20) Position hole Terminal Terminal block block ⑥Terminal block (M-NET)      Connect the lead wire-B ⑩ to both the  connector CN5 on the M-NET board ①  and the connector CNMNT on the  control board. Hole for M-NET ground ※Caution ⑧Label A Wire Marking:NON-INV, Connector  color:White Always make sure that the  markings and the applicable model match.  ①M-NET board ⑫Lead wire-D If used incorrectly, parts could be  damaged.
  • Page 8 M-NET Converter PAC-SF81MA-E 2. Installation procedure  【Applicable model : Group E】 Control board      Attach the Plate 2 ⑮, using two screws ⑤.      Install M-NET board ① (with insulation  sheets and supports) on the Plate2 ⑮ .      ※Push it firmly until you hear it  click .        Use terminal screw ⑦ to secure terminal  block⑥       ※Terminal block⑥ has a round boss for  positioning:Fit the round boss into the  positioning hole in steel-plate.      Paste label ⑧       Use lead wire-A ⑨ to connect CN5 of  M-NET board ① connection and  CNMNT of outdoor control board.      ※Caution Wire Marking:INV type, Connector  color:Red Always make sure that the  CENTRALIZED CONTROL(M-NET) A B S markings and the applicable model  ⑧Label B G79H744H02 match. If used incorrectly, parts could  be damaged. ⑬Ground wire Use lead wire-C ⑪ to connect CND of  M-NET board ① connection and  ⑦Terminal screw CNVMNT of outdoor control board. ...
  • Page 9 M-NET Converter PAC-SF81MA-E 2. Installation procedure  【Applicable model : Group F】      Install M-NET board ① (with insulation  (When viewed from the side of electrical parts box) sheets and supports) on the side of  electric box . At the four point indicated by arrows. Control board      ※Push it firmly until you hear it  click .        Use terminal screw ⑦ to secure terminal  block⑥       ※Terminal block⑥ has a round boss for  positioning:Fit the round boss into the  positioning hole in steel-plate.      Paste label ⑧ under terminal block ⑥      Use lead wire-A ⑨ to connect CN5 of  M-NET board ① connection and  CNMNT of outdoor control board.      ※Caution Wire Marking:INV type, Connector  color:Red  Always make sure that the markings  and the applicable model match. If  used incorrectly, parts could be  damaged. Use lead wire-C ⑪ to connect CND of  M-NET board ① connection and  ①M-NET board CNVMNT of outdoor control board.  Use lead wire-D ⑫ to connect CN2M of  M-NET board ① connection and  terminals A and B of terminal block ⑥  Polarity is not a concern. ※Connect the wire firmly making sure  that the screws on terminal block are ...
  • Page 10 M-NET Converter PAC-SF81MA-E 2. Installation procedure 【Applicable model : Group G】      The M-NET board ① is installed in the  CN2M bottom of electric box so that the DIP  switches (SW11,SW12) come front. SW12 SW11 ①M-NET board      ※Push it firmly until you hear it  click .   (Top view of Electric box without top panel)        Use terminal screw ⑦ to secure terminal  CN2M block⑥  SW12 SW11      ※Terminal block⑥ has a round boss for  positioning:Fit the round boss into the  positioning hole in steel-plate.      Paste label ⑧ under terminal block ⑥      Use lead wire-B ⑩ to connect CN5 of  M-NET board ① connection and  CNMNT of outdoor control board.      ※Caution Wire Marking:NON-INV, Connector  color:White Always make sure that the  markings and the applicable model  (Front view of Electric box) match. If used incorrectly, parts could  be damaged. Use lead wire-C ⑪ to connect CND of  M-NET board ① connection and  CNVMNT of outdoor control board.  Use lead wire-D ⑫ to connect CN2M of  M-NET board ① connection and ...
  • Page 11 M-NET Converter PAC-SF81MA-E 2. Installation procedure 【Applicable model : Group H】 E-219...
  • Page 12 M-NET Converter PAC-SF81MA-E 3. Wiring method for M-NET (1) Attention ① Outside of the unit, the wires for transmission (called for transmit wires later) should keep away (5 cm      or more) from power cable not to receive electric noise.  (Never put the transmit wires and power cable      in the same cable pipe.) ② Never supply voltage 220V-240V to the terminals (TB7) for transmission.  If the voltage is supplied, it      can break the electronic parts on the A-M CONVERTER board. ③ Use the shielded cable (CVVS, CPEVS) of 1.25mm square thickness with 2 wires for the transmission      cable.  Never use transmit wires of different system with a cable which contains multi wires. The      communication of transmit signals will not work properly and it can cause wrong operation.   Group remote  Refrigerant address Refrigerant address Refrigerant address controller M-NET address M-NET address M-NET address Power supply unit for transmit cable (                ) (                ) (                ) Slim A control Slim A control Slim A control remote control remote control remote control Between the outdoor units, it is OK that only M-NET wiring (2 wires, no polarity) is done. (2) M-NET address setting      Make M-NET setting and refrigerant address setting on only outdoor unit.        There is no address settings for outdoor unit and remote controller like City Multi system.            The M-NET address setting for taking into centralized control system should be done only to the       outdoor unit.        The address set number should be 1-50 same as for City Multi indoor unit and make set in order of ...
  • Page 13 M-NET Converter PAC-SF81MA-E (3) Refrigerant address setting      In case that the A control Slim is set for group between different refrigerant (when multiple refrigerant       system is set in one group), it is necessary to make refrigerant address setting besides the wiring for       remote controller (TB5) between the indoor untis.        In case that the group setting is not done, be sure to leave the refrigerant address set for 00.        The refrigerant address is set by dip switch SW1 (3-6) on the outdoor controller of the outdoor unit.        (Factory settings are all OFF ・・・・・Refrigerant address 00). (SW1) 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6...
  • Page 14 M-NET Converter PAC-SF81MA-E Attention for A control Slim M-NET connection Pay attention to the next points for wiring of shielded wires. CAUTION It can cause the transmission error due to noise. The shielded wires of M-NET transmission should be  connected with the ground wire at any only one place of   Outdoor unit digital LED display reads "Ed" error. the unit to be connected.  Centralized control remote controller reads "0403" error. ×Bad example (Multiple ground of shielded wire) ○Good example (One spot ground of shielded wire)   ※ Centralized  Outdoor unit  Outdoor unit  Outdoor unit  Outdoor unit  Outdoor unit  Outdoor unit  Power supply  Centralized  Power supply  control remote  corresponds corresponds corresponds unit control remote  corresponds corresponds corresponds unit controller  to M-NET  to M-NET  to M-NET controller  to M-NET...