The secure isolation of contact-dangerous electrical circuits is only guaranteed when the connected devices fulfill the requirements of the DIN VDE 0106 T.101 (basic requirements for secure isolation). For secure isolation, run the supply lines separated from contact-dangerous electrical circuits or additionally isolate them. 4 - EN SensyTemp TSP CI/TSP-EN...
VDE 0165/08.98 (=EN 60 079-14/1997 as well as IEC 60 079-14/1996) about the intrinsic safety of the interconnection is to be provided. An interconnection certificate for intrinsically safe electrical circuits is to be produced. CI/TSP-EN SensyTemp TSP EN - 5...
After clamping the connection lines using a suitable tool (screwdriver, wrench), ensure that the connection heads are securely closed and sealed. Be sure to observe here that the sealing rings of the connection head are clean and undamaged. 6 - EN SensyTemp TSP CI/TSP-EN...
Insufficient mounting diameter For pipes with very small nominal diameters, an oblique insertion or insertion in an elbow pipe is recommended; whereby the thermowell tip must be positioned against the flow of the medium. Fig. 2 CI/TSP-EN SensyTemp TSP EN - 7...
The temperature sensors must be included in the potential equalization. 3.5.1 Intrinsic safety: ATEX II 1 G EEx ia IIC T6 ... T1, Zone 0, 1, 2 There are no additional specifics that must be observed for the mechanical installation. 8 - EN SensyTemp TSP CI/TSP-EN...
These may no longer be used if they have surface damage in the area of the ingnition penetration-proof seam or the connection head base. • Use only separate ignition-proof certified cable glands of a suitable ignition-proof type. ABB ships standard EEx d approved type ELFIT cable glands. CI/TSP-EN...
Installation • Observe the cable gland approval and installation information. Observe the instruction manual 42/10-57 XU for the ABB supplied cable glands. • Check the line used with regards to suitability (type, actual line diameter, etc.). • Tighten the cable glands until the line is firmly enclosed by the sealing ring.
The documents belonging to the EC prototype inspection document are explicitly part of these operating instructions and must be mandatorily complied with. The temperature sensors must be included in the potential equalization. CI/TSP-EN SensyTemp TSP EN - 11...
Page 14
Field (Ex area) Control room (secure area) Fig. 3 A Transmitter B Feed separator / SPS input with feed Note Observe the “Technical specifications” and “Explosion-protection technical data” chapters (see data sheet and/or operating instructions). 12 - EN SensyTemp TSP CI/TSP-EN...
2-, 3-, or 4-wire connection. Only one measurement circuit may be connected for the protection type EEx i for double measurement elements (z.B. 2 x Pt100). ABB transmitters are internally switched so that 2 measurement elements may also be connected since both elements are integrated into the same EEx I sensor circuit.
For use of double measurement circuits (2 x Pt100, 2 x thermocouple, 2 installed transmitters in the connection head), the sum of the voltages, currents and power may not exceed the electrical and thermal parameters. See chapter “Thermal data“ in the operating instructions. 14 - EN SensyTemp TSP CI/TSP-EN...
4-wire circuit Fig. 5 In accordance with EN 60751 (IEC 60751) Dual 2-wire circuit 3-wire circuit 4-wire circuit Fig. 6 yellow black W white 4.2.2 Thermocouple In accordance with EN 60584 Single Dual Fig. 7 CI/TSP-EN SensyTemp TSP EN - 15...
Only one measurement circuit may be connected for the protection type EEx i for double measurement elements (e.g. 2 x Pt100). ABB transmitters are internally switched so that 2 measurement elements may also be connected since both elements are integrated into the same EEx I sensor circuit.
Page 19
4.2.3.1. 4.2.3.3 Dust-ignition proof and intrinsic safety: ATEX II 1 D IP6X T133...T400 and ATEX II 1 G Ex ia IIC T6...T1, Zone 0, 1, 2, 20, 21, 22 See chapter 4.2.3.1. CI/TSP-EN SensyTemp TSP EN - 17...
Page 20
See chapters 4.2.3.3 and 4.2.3.4. 4.2.3.6 ATEX Ex nA - Zone 2 and 22 Ex area Zone 2 and 22 Secure area Fig. 11 A Temperature sensor C Housing with IP 6X B Sensor connection wires D Transmitter 18 - EN SensyTemp TSP CI/TSP-EN...
See ABB documentation 10/63-0.50. Fieldbus The instruction manual for the selected transmitter is included in the delivery by ABB. This information is additionally available for download on the Internet at www.abb.com/temperature. The technical data of the selected transmitter must be complied with.
Page 22
Hermetically sealed: ATEX II 1/2 G Ex d IIC T6 ... T4, Zone 1 Ex area Zone 1 Secure area Fig. 14 A Measuring inset in thermowell C EEx d approved housing (IP6X) with EEx d cable gland B Transmitter in connection head D Feed separator 20 - EN SensyTemp TSP CI/TSP-EN...
The relevant safety and accident prevention regulations must be complied with. • The associated technical documentation for the operation of transmitters and indicator units is to be observed. The technical documentation is also available on the Internet at www.abb.com/temperature. CI/TSP-EN SensyTemp TSP EN - 21...
For information about using the LC display for parametrization of the transmitter, see the OI/TSP operating instructions. Appendix Note All documentation, declarations of conformity and certificates are available in the download area of ABB Automation Products GmbH. www.abb.com/temperature Additional documents • Operating Instructions (OI/TSP) •...