SAFETY PRODUCTS
Eden DYN
Coded non-contact safety sensor
Product Manual
2TLC172271M0201
Rev D
ORIGINAL INSTRUCTIONS

Advertisement

Table of Contents
loading

Summary of Contents for ABB Eden DYN

  • Page 1 — SAFETY PRODUCTS Eden DYN Coded non-contact safety sensor Product Manual 2TLC172271M0201 Rev D ORIGINAL INSTRUCTIONS...
  • Page 2 ABB JOKAB SAFETY’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by ABB JOKAB SAFETY. ABB JOKAB SAFETY MAKES NO WARRANTY OR REPRESENTATION, EXPRESSED OR IMPLIED, REGARDING NON-...
  • Page 3: Table Of Contents

    Table of Contents Introduction ..........................5 Scope ..............................5 Audience ..............................5 Prerequisites ............................5 Special notes ............................5 Overview ..........................6 General description ..........................6 Safety regulations ..........................6 Models of Adam and Eva ....................... 7 Adam DYN .............................. 7 Eva ................................
  • Page 4 How to program a new Adam without code, to accept a new Eva ..........21 How to erase existing codes from Adam ..................21 Replacing Eva (Not needed for General to General switch).............. 21 Testing the safety functions ......................22 Info output (pin-5) –...
  • Page 5: Introduction

    This document is intended for authorized installation personnel. Prerequisites It is assumed that the reader of this document has knowledge of the following: • Basic knowledge of ABB Jokab Safety products. • Knowledge of machine safety. Special notes Pay attention to the following special notes in the document:...
  • Page 6: Overview

    2 Overview General description Eden DYN sensor consists of two separate devices – Adam and Eva – intended for use as interlocking device for gates, hatches etc. Eva can be general coded or unique coded. Eden DYN meets the coding requirements according to EN ISO 14119:2013 regarding manipulation protection.
  • Page 7: Models Of Adam And Eva

    Requires a Pluto as master. (For more information about the Pluto, refer to the user manual at www.abb.com/jokabsafety) Eva exists in two different models: Eva General code and Eva Unique code. It is possible to mix different models of Eva in the same safety circuit.
  • Page 8: Electrical Connections

    4 Electrical connections NB: Use a suitably insulated low-voltage supply system type SELV or PELV. Adam DYN-Info M12-5 M12 5-pole male M12 5-pole female from cable side from cable side M12-connector: (5-pole male) 1 ) Brown: +24 VDC 2 ) White: Dynamic signal in 3 ) Blue: 0 VDC...
  • Page 9: Adam Dyn-Status M12-5

    Dynamic signal in 3) Blue: 0 VDC 4) Black: Dynamic signal out 5) Grey: Info/StatusBus NB: The use of shielded cable is recommended for enhanced electromagnetic immunity. Caution! All cable colors according to ABB Jokab Safety standard cables. 2TLC172271M0201 Rev D...
  • Page 10: Connection Of Cable C5 To M12 C01 And M12 C02 Connectors

    Parallel connection with Eden, Tina and Spot Eden can be connected in parallel with a Tina unit, a pair of Spot 10 or another Eden DYN in a safety circuit, to create a muting/bypass function. M12-3B can be used for an easy connection. For Adam DYN-Status in StatusBus mode use M12-3S.
  • Page 11: Connection Of Reset Button To Adam Dyn-Reset

    The maximum current consumption for the indication lamp is 30 mA. Smile 12RF is a reset button with indication lamp from ABB Jokab Safety intended to be used together with Adam DYN-Reset. The minimum current consumption needed through the lamp is 10 mA. If no lamp is used, a 4.7 kOhm resistor can be used instead.
  • Page 12: Serial Connection

    Serial connection Serial connection of three Adam DYN-Reset with Smile 12 RF to Pluto or Vital via M12-3A. 2TLC172271M0201 Rev D...
  • Page 13: Connection Examples

    5 Connection examples Adam DYN-Info connected to Vital 1 B) Adam DYN-Info connected to Vital 1 with manual A) Adam DYN-Info connected to Vital 1 with reset. automatic reset. 2TLC172271M0201 Rev D...
  • Page 14: Several Adam Dyn-Info Connected In Series To Vital 1

    Several Adam DYN-Info connected in series to Vital 1 A) Three Adam DYN-Info connected to Vital 1 with automatic reset. Several Adam DYN-Status connected in series to Pluto A) Two Adam DYN-Status connected to a Pluto Safety PLC. Left unit connected to use StatusBus, right unit connected to use Info. 2TLC172271M0201 Rev D...
  • Page 15: Several Adam Dyn-Status Connected In Series To Pluto Via M12-3S

    Several Adam DYN-Status connected in series to Pluto via M12-3S A) Three Adam DYN-Status connected to a Pluto Safety PLC via M12-3S to use StatusBus. 2TLC172271M0201 Rev D...
  • Page 16: Y-Connectors

    Y-connectors M12-3A M12-3B M12-3S 2TLC172271M0201 Rev D...
  • Page 17: Installation

    6 Installation General information Warning! All the safety functions must be tested before starting up the system. • Note that the detection distance can be affected when Eden is mounted close to metal. • The Eden can be mounted on metal but must not be surrounded. •...
  • Page 18: Detection Distance

    Detection distance Eva can be turned in several different ways relative to Adam, see details in the figure below. The green fields in the picture show the detection range of Adam relative to Eva. The Eva is detected when the two coils (see red-marked areas, image below) in Eva are in contact with the green field. The figures above shows maximum detection distances.
  • Page 19: Mounting

    Mounting Depending on the cable connector used for the connection to Eden, one or two distance plates might be required for correct mounting in order to avoid damaging Adam. It is recommended to use the distance plates DA 1B, supplied with the Adam, see figure below. Also, the mounting spacers DA 2B supplied must be used in order to physically protect Eden from damage.
  • Page 20: Mounting Procedure

    Mounting procedure Fasten each sensor with two M4-screws. Safety screw SM4x20 (2TLA020053R4200) is recommended. The DA 2B mounting spacers must be used in order to physically protect Eden from damage. Use max tightening torque 1.0 Nm on screws. 2. Lock screw with Loctite or similar if necessary, to prevent easy dismounting (refer to risk assessment).
  • Page 21: Teaching The Code

    Teaching the code Adam is without code in its factory setting mode and need to be programmed with the code from an Eva (General or Unique coded). The code of the first Eva detected by the Adam is automatically programmed as soon as Eva is within the detection distance. If Adam is programmed to accept an Eva with a general code, it will accept all Eva units with a general code.
  • Page 22: Testing The Safety Functions

    Testing the safety functions Make sure the safety unit and safety module (Vital/Pluto/URAX) is working properly by following these steps: Interrupt Eden output by moving Eva away from Adam. The LED will light red when Eva is out of range of Adam. 2.
  • Page 23: Info Output (Pin-5) - Information/Statusbus

    Pluto or FIXA) to obtain a valid operational address 1–30. This can be done manually or automatically done using ‘Pluto Manager StatusBus Teach addresses’ functionality. For more information about the StatusBus, refer to the user manual for Pluto at: www.abb.com/jokabsafety StatusBus message from slave contains 3 information bits. •...
  • Page 24: Led Indication

    7 LED indication The non-safe status LED on Adam shows the status of the Eden sensor and the output status as follows: LED on Adam Description Safety circuit Green Valid Eva within range Closed Flashing green Valid Eva within range, waiting for reset Open Flashing red/green Valid Eva within range, no valid in signal...
  • Page 25: Maintenance

    (EN 62061:2005). Warning! In case of breakdown or damage to the product, contact ABB Jokab Safety. Do not try to repair the product. It might accidentally cause permanent damage, impairing the safety of the...
  • Page 26: Compatibility With Analog Models Of Eden

    • It is not possible to use an analog Eva with a digital Adam DYN. • The info output switches from +24 V to 0 V on analog models of Eden. Eden DYN has only a +24 V/Info output. •...
  • Page 27: Model Overview

    Model overview Type Article number Description Adam DYN-Info M12-5 2TLA020051R5100 Pin 5: Information Adam DYN-Reset M12-5 2TLA020051R5300 Pin 5: Reset/Indication Adam DYN-Status M12-5 2TLA020051R5200 Pin 5: Information /StatusBus Eva General code 2TLA020046R0800 General code Eva Unique code 2TLA020046R0900 Unique code Accessories Type Article number...
  • Page 28: Cables With Connectors

    Cables with connectors Connector Female/male Length Special feature Type Article number M12-5 Female M12-C61 2TLA020056R0000 Harsh environment, M12-C61HE 2TLA020056R8000 halogen free M12-C101 2TLA020056R1000 10 m Harsh environment, M12-C101HE 2TLA020056R8100 halogen free 20 m M12-C201 2TLA020056R1400 2TLA020056R5800 Female + male M12-C0312 0.3 m 0.06 m M12-C00612...
  • Page 29: Separate Cables And Connectors

    Separate cables and connectors Description Type Article number Connectors M12-5 pole female, straight M12-C01 2TLA020055R1000 M12-5 pole male, straight M12-C02 2TLA020055R1100 M12-8 pole female, straight M12-C03 2TLA020055R1600 M12-8 pole male, straight M12-C04 2TLA020055R1700 Cable with 5 conductors 10 m cable with 5 x 0.34 shielded conductors C5 cable 10 m 2TLA020057R0001 50 m cable with 5 x 0.34 shielded conductors...
  • Page 30: Technical Data

    11 Technical data Manufacturer Address ABB Electrification Sweden AB, Jokab Safety Varlabergsvägen 11 SE-434 39 Kungsbacka Sweden Power supply Rated operating voltage +24 VDC +15 % -40 % Use SELV/PELV Current consumption 30 mA at 24 VDC 35 mA at 18 VDC...
  • Page 31 Information for use in USA / Canada Enclosure Type 1, 4, 4x Intended use Applications according to NFPA 79 Power source Only suitable for use in a limited voltage / current circuitry. The limited voltage / current source must comply with one of the following: a) An isolating device such that the maximum open circuit voltage potential available to the circuit is not more than +24 VDC and...
  • Page 32: Guideline For Chemical Resistance

    Guideline for chemical resistance Chemicals Eden DYN Hydrocarbons aliphatic Good aromatic Good halogenated - fully Poor/Fair - partly Poor Alcohols Good Phenols Poor Ketones Fair/ Good Amines Not tested Esters Fair/ Good Ethers Good Acids inorganic Good organic Fair oxidizing...
  • Page 33: Eden Dimensions

    Eden dimensions Adam M12, contact seen from outside. NB: All dimensions in millimeters. CAD model For CAD models please visit www.abb.com/jokabsafety 2TLC172271M0201 Rev D...
  • Page 34: Ec Declaration Of Conformity