UPS5000-(200 kVA-800 kVA) Top Air-flow Cabinet
User Manual
Figure 3-15 Removing the cable trough cover and fan interconnection terminal protective cover
Step 2 Connect the ground cable of the top air-flow cabinet to the nearest beam of the UPS cabinet.
Figure 3-16 Connecting the ground cable of the top air-flow cabinet
Step 3 Connect the power cable and signal cable of the top air-flow cabinet to the UPS.
1.
Issue Draft A (2016-12-09)
Pull out the power cable (04093521-07) from the cable trough of the top air-flow cabinet,
bind the cable along the post of the top air-flow cabinet, and connect the cable from the
side beam of the UPS to the small holes on the UPS output U and output N copper bars.
The 300K-SM cabinet, whose power distribution subrack is in the lower part, is used as an example
to show how to connect cables.
The 200K-FM cabinet, whose power distribution subrack is in the upper part, is used as an example
to show how to connect cables.