ABB RELION REX640 Operation Manual page 95

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759118 A
REX640
Operation Manual
Fault indication
Conf.error,slot E
Conf.error,slot A2
Conf.error,slot B
Conf.error,slot D
Conf.error,slot F
Conf.error,slot G
Conf.error,slot A1
Card error,slot C
Card error,slot E
Card error,slot A2
Card error,slot B
Card error,slot D
Card error,slot F
Card error,slot G
Card error,slot A1
Prod license error
RAM error
ROM error
EEPROM error
FPGA error
RTC error
COM card error
Fault code
-31
-32
-33
-34
-35
-36
-37
-40
-41
-42
-43
-44
-45
-46
-47
-62
80
81
82
83
84
116
Section 6
Troubleshooting
Additional information
Module in slot E is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot A2 is wrong type,
is missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot B is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot D is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot F is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot G is wrong type, is
missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot A1 is wrong type,
is missing, does not belong to
original configuration or module
firmware is faulty.
Module in slot C is faulty.
Module in slot E is faulty.
Module in slot A2 is faulty.
Module in slot B is faulty.
Module in slot D is faulty.
Module in slot F is faulty.
Module in slot G is faulty.
Module in slot A1 is faulty.
Error in product license
Error in the RAM memory on the
CPU module
Error in the ROM memory on the
CPU module
Error in the EEPROM memory
on the CPU module
Error in the FPGA on the CPU
module
Error in the RTC on the CPU
module
Error in the COM module
89

Hide quick links:

Advertisement

Table of Contents
loading