Commissioning
7.5.2.3
122
GUID-94687084-2B9A-45D4-AD4A-D022CA593124 V1 EN
Figure 105:
Send Events page

Checking GOOSE data

1.
On the GOOSE Receiving page, check the GOOSE data that the relay
subscribes from the Ethernet network.
The left side of this page shows a list of devices that send GOOSE messages to
the relay. These devices that publish data for the relay are defined in the relay
configuration. The right side of the page shows the GOOSE data the relay
receives from the network. The data set consists of value and quality attributes.
The received data has status indicators where green means all OK, yellow
warning and red error.